Back to page

ICS Schneider Messtechnik
ICS Schneider Messtechnik – Kontakt

TEST PROBES - DSP

TEST PROBES - DSP

The MultiSafe DSP is equipped with a thread for fast and safe extension with test probes. With the test probes, the MultiSafe DSP can be used perfectly and safely in various applications.

ATTENTION! The probes are listed here per piece.

Insertion prod:

  • safe up to 1000 V AC / 1500 V DC
  • to check by self-test of the MultiSafe

Flexible pin prods:

  • safe up to 1000 V AC / 1500 V DC
  • to check by self-test of the MultiSafe
  • the bare electrode length is shortened to < 4 mm
  • flexible pin prod for testing on tight terminal strips or contacts

Extensions:

  • safe up to 1000 V AC / 1500 V DC
  • to check by self-test of the MultiSafe
  • allow more safety distance during testing
  • allow immersion between bare busbars and cables
  • various electrode shapes for testing on busbars and overhead lines

Other special test probes and electrode shapes on request.

 

There are two connections for probes to the MultiSafe:

1. attachable connection
A profile rubber provides a secure hold on the probes of the DSP.

2.screwable connection
Absolutely strong connection even under tensile load and vibration, waterproof and dustproof.
To do this, the MultiSafe must be equipped with threads on the test probes. A retrofit is possible. Attachable DSP accessories continue to fit.
The list in the table below shows which probes can be used with or without thread set.

 

DSP-S20-A DSP-S57 DSP-S56 DSP-110 DSP-S550 DSP-S850
Application Insertion prod flexible pin prod for test holes Extension for more safety distance
Nominal voltage range 50 – 1 000 V AC
50 – 1 500 V DC
Nominal frequency range DC / 15 – 500 Hz
Probe length 20 mm 57 mm 56 mm 110 mm 550 mm 855 mm
Overvoltage category CAT IV 600 V
CAT III 1000 V
Connection screwable attachable screwable
Protection category IP 65
available electrode shape hardened
pin prod
flexible pin prod
3 mm
Y-Electrode for overhead lines

i-Electrode for busbars and measuring points

changeable electrode shape no yes
Art.-No. 84321 84013 84315 84318 84010 84014
Dimensions and weight 140 x 30 x 30 mm

40 g

145 x 20 x 20 mm

15 g

180 x 30 x 30 mm

40 g

235 x 30 x 30 mm

40 g

550 x 30 x 30 mm

90 g

860 x 30 x 30 mm

120 g