A service technician is testing a 2-wire pressure transmitter using a portable process calibrator. The integrated 24 V loop power supply is switched on, the transmitter starts up and provides a plausible 4–20 mA signal at low measured values. As the test pressure increases, the current initially rises as expected. However, shortly before reaching the upper range value, the indication stops below 20 mA. The transmitter appears to be failing the calibration requirements.
The cause does not necessarily lie in the pressure sensor or its electronic characteristic curve. The actual supply voltage available in the measuring circuit may be insufficient. The PLC analogue input, an activated HART resistor, the connecting cables and the current measurement function of the calibrator cause voltage drops. Consequently, only the remaining portion of the 24 V supply is available to the transmitter.
A current loop operates reliably only as long as the connected instruments remain within their permissible voltage and load limits. Particularly at high loop currents, the voltage drop across resistive loads increases. A measuring circuit may therefore operate correctly at 4 mA but already reach its operating limits at 20 mA. In the overrange region or at a high fault current, the available voltage margin may be completely exhausted.
This technical article explains how to correctly evaluate the 24 V loop power supply of a calibrator. It focuses on burden voltage, maximum permissible loop resistance, minimum transmitter voltage, current measurement, HART resistors and the actual load capacity of the calibrator. A calculation example demonstrates why a measuring circuit may still operate at 20 mA but fail at 22 mA. The article also covers test setups, measurement uncertainty, calibration procedures, typical faults and suitable process calibrators from the ICS Schneider product range.
Table of Contents
- Define the Test Task and the Complete 4–20 mA Measuring Circuit
- Understand the Electrical Operating Principle of a 2-Wire Current Loop
- Distinguish Measuring, Sourcing, Simulating and Loop Power Functions
- Distinguish the Nominal 24 V Supply from the Actually Available Voltage
- Correctly Calculate Load Resistance and Burden Voltage
- Establish the Voltage Budget of the Complete Measuring Circuit
- Determine the Maximum Permissible Loop Resistance
- Calculation Example: 24 V, 550 Ω Load and 22 mA Loop Current
- Consider the Effect of a 250 Ω HART Resistor
- Check the Calibrator’s Internal Burden During Current Measurement
- Evaluate Cable Resistance and Contact Resistance
- Distinguish Calibrator Output Capacity and Load Limits
- Correctly Connect 2-Wire, 3-Wire and 4-Wire Transmitters
- Choose the Correct Test Setup with Internal or External Power
- Systematically Measure Voltage Drops Under Actual Load
- Test 4 mA, 12 mA, 20 mA and Overrange Conditions Separately
- Check Supply Stability, Battery Condition and Dynamic Behaviour
- Evaluate Reference Accuracy and Calibration Measurement Uncertainty
- Consider Reverse Polarity, External Power and Ex Requirements
- Perform a Systematic Testing and Calibration Procedure
- Diagnose Typical Fault Patterns and Their Causes
- Suitable Loop and Process Calibrators from ICS Schneider
- Conclusion: Available Voltage Margin Matters, Not Just the 24 V Indication
- Frequently Asked Questions About 24 V Loop Power from Calibrators
1. Define the Test Task and the Complete 4–20 mA Measuring Circuit
A 4–20 mA current loop transmits industrial process values as an electrical current. It is used, for example, with pressure, temperature, flow and level transmitters.
A portable process calibrator is frequently used to test such a measurement point.
Depending on the instrument configuration, it can measure or source defined current values, simulate a 2-wire transmitter or provide an internal supply voltage.
Particularly when testing with an integrated 24 V loop supply, it is first necessary to establish which instruments actually form part of the measuring circuit.
A simple test setup may consist of a calibrator, a 2-wire transmitter and test leads.
In an existing process installation, additional components may be connected. These include PLC analogue inputs, isolating amplifiers, HART resistors, indicating instruments and possibly other series-connected measuring circuit components.
Each component can affect the available voltage.
If the function of the complete measuring circuit is to be verified, the test task must therefore be considered beyond the simple measurement of current.
It is particularly important to distinguish between electrically testing a transmitter and performing its complete process calibration.
During the calibration of a pressure transmitter, for example, a defined reference pressure is applied and the actual output current is measured.
A current signal that no longer reaches its target value because of insufficient supply voltage must not be interpreted as a pressure transmitter characteristic error without further investigation.
2. Understand the Electrical Operating Principle of a 2-Wire Current Loop
A conventional 2-wire transmitter uses the same two conductors for its electrical power supply and measurement signal transmission.
The transmitter requires sufficient operating voltage to power its electronics, sensing element and current regulation circuitry.
Within its specified operating range, it adjusts the loop current according to the measured process value.
With a linear assignment of 0 … 100 % to 4 … 20 mA, the lower range value corresponds to 4 mA and the upper range value to 20 mA.
Intermediate measured values are represented according to the selected characteristic curve.
The current passes through all series-connected components of the measuring circuit.
These include the transmitter, the electrical supply and the loads that actually act in series.
As long as the supply provides sufficient voltage, the transmitter can regulate the current within its specified limits.
If the available voltage falls below the required operating range, the current regulation function may no longer operate correctly.
For example, the output current may remain below the requested value or become unstable.
The exact response depends on the transmitter being used.
An important principle is therefore that current is the transmitted measurement quantity, but adequate supply voltage is a necessary operating condition.
3. Distinguish Measuring, Sourcing, Simulating and Loop Power Functions
Modern loop calibrators offer different electrical operating modes.
These modes must not be confused during wiring or interpretation.
In the basic mA measurement mode, the calibrator measures the current of an already powered circuit. The electrical power normally comes from an external source.
In mA measurement with internal loop power mode, the calibrator additionally provides the power required by a suitable 2-wire transmitter.
In active mA sourcing mode, the calibrator generates a defined current itself. This can be used, for example, to test a passive PLC current input.
In 2-wire transmitter simulation mode, the calibrator performs the function of a passive, loop-powered current regulator. The required energy is supplied by a suitable external power source.
| Operating Mode | Measuring Circuit Power Supply | Calibrator Function | Typical Test Task |
|---|---|---|---|
| Measure mA | External loop power | Measures the existing current | Check the current signal of an operating transmitter |
| Measure mA with 24 V loop power | Internal calibrator power supply | Powers the device under test and measures its current | Test a 2-wire transmitter without external power |
| Actively source mA | Provided internally, depending on instrument configuration | Regulates a defined output current | Test a passive PLC analogue input |
| Simulate a 2-wire transmitter | External power supply required | Regulates current as a passive transmitter simulator | Test an existing current loop without the actual transmitter |
The actual terminal assignments and available operating modes depend on the calibrator.
Particularly with current simulation, it is important to understand the difference between an active current output and a passive current sink.
An active current source must not be connected against an existing active voltage or current supply without the appropriate instrument approval.
A detailed general description of these operating modes is provided in the ICS technical article Testing 2-Wire Transmitters with a Process Calibrator: Understanding Measurement, Simulation and Loop Power.
This article, however, focuses on whether the electrical supply is sufficient under the load actually present.
4. Distinguish the Nominal 24 V Supply from the Actually Available Voltage
Many process calibrators have an integrated loop power supply with a nominal voltage of 24 V DC.
However, this specification does not mean that the connected transmitter always has 24 V available under all operating conditions.
The supply must first overcome the voltage drops across the series-connected components of the measuring circuit.
The remaining voltage is then available to the transmitter.
For a simplified analysis:
UQuelle = UTransmitter + UBürde + ULeitung + Usonstige
UQuelle is the actual loop supply voltage provided under load.
UTransmitter denotes the operating voltage remaining at the transmitter.
The additional voltage contributions result from load resistors, cables and other series-connected components.
For example, if the external loads produce a total voltage drop of 10 V at a loop current of 20 mA, an idealised 24 V supply leaves 14 V available to the transmitter.
If the transmitter requires at least 12 V, a voltage margin of 2 V remains under these conditions.
Such a margin must be checked at the intended maximum current and under the least favourable permissible supply conditions.
Particularly with battery-powered calibrators, an exactly constant output voltage under every load condition must not be assumed without a corresponding manufacturer specification.
The nominal 24 V function and the actual guaranteed output voltage or load capacity must therefore be evaluated separately.
5. Correctly Calculate Load Resistance and Burden Voltage
In a 4–20 mA current loop, the term burden refers to the electrical load that the current output must drive.
For an ohmic resistance, the corresponding voltage is determined using Ohm’s law:
UBürde = I · RBürde
Here, I represents the loop current and RBürde represents the load resistance.
A common example is a 250 Ω measuring resistor.
At 4 mA, the voltage drop is:
U = 0.004 A · 250 Ω = 1 V
At 20 mA:
U = 0.020 A · 250 Ω = 5 V
The resistance remains unchanged, but the voltage drop increases proportionally with the current.
At an increased current of 22 mA, the same resistor would already require 5.5 V.
This voltage is no longer available to the transmitter.
If several ohmic loads are connected in series, their resistances are added:
Rgesamt = R1 + R2 + … + Rn
This simplified calculation applies to resistive loads.
Electronic inputs and measuring instruments, on the other hand, may introduce their own voltage drops that cannot always be fully represented by a constant resistance.
In such cases, the relevant manufacturer specifications or the actual measured voltage drops must be used.
6. Establish the Voltage Budget of the Complete Measuring Circuit
To ensure reliable 24 V loop power, the sum of all voltage drops must be known.
In a typical test circuit, the PLC input, cabling and any HART resistor must be taken into account.
The calibrator itself may also introduce an additional voltage drop in a particular operating mode.
The complete simplified voltage budget can, for example, be expressed as:
UTransmitter = UQuelle − I · Rgesamt − Uzusätzliche
Here, Rgesamt includes all ohmic resistances actually acting in series.
Uzusätzliche represents additional voltage drops not already included in this resistance total.
It is particularly important not to count any resistance twice.
A PLC input with 250 Ω may, for example, already provide the load conditions required for HART communication.
If another 250 Ω resistor is connected in series, the total burden increases.
However, if an integrated HART resistor is intended only as an alternative to an existing external resistor, both must not automatically be included in the calculation simultaneously.
The components that actually affect the circuit are determined by the real wiring and calibrator settings.
The existing circuit should therefore be traced or a clear wiring diagram prepared before testing.
Only then can the available voltage margin be calculated correctly.
7. Determine the Maximum Permissible Loop Resistance
A 2-wire transmitter requires a certain minimum operating voltage.
This is usually specified in the data sheet.
If the supply voltage is known, the maximum permissible external resistance for a specified loop current can be calculated.
Under idealised conditions:
Rmax = (UQuelle − UTransmitter,min) / Imax
With a 24 V supply, a minimum transmitter operating voltage of 12 V and a maximum current of 20 mA:
Rmax = (24 V − 12 V) / 0.020 A = 600 Ω
Under these simplified conditions, a maximum of 600 Ω is therefore available for all external ohmic loads.
This limit does not yet include any additional required voltage margin.
If, for example, an additional margin of 2 V is allowed, the calculated resistance is reduced to:
Rmax,Reserve = (24 V − 12 V − 2 V) / 0.020 A = 500 Ω
Selection of the relevant current is particularly important.
Depending on its configuration, a 4–20 mA transmitter may also output overrange and fault currents above 20 mA.
If the measuring circuit must operate up to 22 mA, for example, this higher current must be used when calculating the load.
Without any additional voltage margin:
Rmax,22mA = (24 V − 12 V) / 0.022 A ≈ 545 Ω
The maximum permissible resistance is therefore lower than in the calculation using 20 mA.
This relationship is also used in manufacturers’ data sheets. For example, WIKA specifies the permissible load of certain 2-wire pressure sensors as a function of supply voltage and minimum operating voltage.
The specifications of the actual transmitter configuration must always be used for the final design.
8. Calculation Example: 24 V, 550 Ω Load and 22 mA Loop Current
A 2-wire transmitter is operated using an idealised constant loop supply voltage of 24 V.
For this calculation example, the transmitter is assumed to require a minimum operating voltage of 12 V.
The current loop contains a PLC input with 250 Ω, an additional 250 Ω HART resistor connected in series, and cable and contact resistances totalling 50 Ω.
These resistances are deliberately considered as three separate loads in this example.
The total resistance is:
Rgesamt = 250 Ω + 250 Ω + 50 Ω = 550 Ω
At 20 mA, the voltage drop is:
ULast,20mA = 0.020 A · 550 Ω = 11.0 V
The voltage remaining at the transmitter is:
UTransmitter,20mA = 24 V − 11.0 V = 13.0 V
The minimum operating voltage of 12 V is still maintained. However, the calculated voltage margin is only 1.0 V.
If the loop current increases to 22 mA, the voltage drop also increases:
ULast,22mA = 0.022 A · 550 Ω = 12.1 V
The remaining voltage is then:
UTransmitter,22mA = 24 V − 12.1 V = 11.9 V
In this simplified model, the transmitter therefore receives less than the assumed required minimum voltage.
| Loop Current | Voltage Drop Across 550 Ω | Voltage at Transmitter | Margin Relative to 12 V |
|---|---|---|---|
| 4 mA | 2.2 V | 21.8 V | +9.8 V |
| 12 mA | 6.6 V | 17.4 V | +5.4 V |
| 20 mA | 11.0 V | 13.0 V | +1.0 V |
| 22 mA | 12.1 V | 11.9 V | −0.1 V |
The example demonstrates why a current loop may operate correctly at low currents but fail at high currents.
At 20 mA, the required minimum voltage is still available under the assumed conditions.
At 22 mA, however, it falls below the required minimum.
The transmitter may consequently be unable to regulate the required current reliably.
It is important to note that this example does not yet include an additional voltage drop caused by a separately connected current measurement function.
A lower actual available loop supply voltage would also make the situation worse.
If the additional 250 Ω HART resistor is not required and is actually removed from the circuit, the total ohmic load in the example is reduced to 300 Ω.
At 22 mA, the resulting voltage drop is then only 6.6 V.
Assuming the constant 24 V supply, the transmitter would again have 17.4 V available.
The calculation therefore clearly demonstrates how significantly an additional series resistor can affect the voltage margin.
All figures are illustrative. They do not represent the load limit of any particular calibrator or transmitter.
The actual voltage, permissible current and maximum supported load must be evaluated using the manufacturers’ specifications and suitable testing.
9. Consider the Effect of a 250 Ω HART Resistor
HART communication combines an analogue 4–20 mA current signal with superimposed digital communication.
To ensure reliable signal transmission, the measuring circuit must meet suitable electrical load or impedance requirements.
A 250 Ω resistor is commonly used for this purpose in many HART applications.
At 20 mA, such a resistor causes a DC voltage drop of 5 V.
This voltage drop must not be overlooked when designing the electrical circuit.
The Druck UPS4E, for example, features an integrated 250 Ω resistor to support HART communication.
The Druck DPI802 also has a corresponding switchable HART loop resistor.
During testing, it must be established whether this resistor actually acts as an additional series load in the selected operating mode.
If a suitable load resistance is already present in the PLC input, a second resistor may be unnecessary.
However, the resistor must not simply be removed if doing so would eliminate the conditions required for the intended HART communication.
The correct solution depends on the actual circuit and the specifications of the HART instrument.
It is also important to distinguish between the presence of a 250 Ω resistor and a complete HART communicator.
An integrated HART resistor provides suitable electrical conditions, but this does not automatically mean that the calibrator supports all digital HART communication functions.
For loop testing, both the actual resistance and the required HART functionality should therefore be documented.
10. Check the Calibrator’s Internal Burden During Current Measurement
A current measuring instrument is normally connected in series with the circuit to measure the loop current.
Even a high-quality calibrator does not necessarily have zero electrical influence on the circuit.
Its internal current measurement circuitry may cause a voltage drop.
This is frequently referred to as the internal burden or burden voltage.
Its magnitude depends on the instrument design, selected measuring range and operating mode.
With a conventional measuring resistor, the relationship can be described using Ohm’s law.
However, the actual burden voltage of electronically regulated or protected measuring circuits may be more complex.
The corresponding calibrator specification is therefore decisive for an accurate assessment.
For example, if an additional series-connected current measurement instrument causes a voltage drop of 0.8 V under a particular operating condition, this 0.8 V is no longer available to the transmitter.
This is particularly critical if the previous load calculation showed a voltage margin of only 0.5 or 1.0 V.
The connection terminals of the calibrator are also important.
Some instruments have separate terminals or measurement functions for basic current measurement, active current sourcing, passive simulation and loop power.
The internal burden may differ depending on the connection and operating mode.
The actual test setup must therefore be evaluated using the relevant operating instructions.
11. Evaluate Cable Resistance and Contact Resistance
In addition to measuring and load resistors, connecting cables also cause an electrical voltage drop.
The complete conductor path is decisive.
In a 2-wire current loop, current flows through both the outgoing and return conductors.
The resistance can be estimated using:
R = ρ · l / A
Here, ρ denotes the electrical resistivity, l the conductor length and A the conductor cross-sectional area.
In a measuring circuit, the relevant lengths of all series-connected conductor sections must be considered.
For copper conductors, a resistivity of approximately 0.0178 Ω·mm²/m can be used for an approximate calculation at 20 °C.
A simple calculation example considers a cable running 100 m between the calibrator and transmitter, with a conductor cross-section of 0.5 mm².
Because both the outgoing and return conductors must be included, the total effective copper conductor length is 200 m.
R ≈ 0.0178 Ω·mm²/m · 200 m / 0.5 mm² = 7.12 Ω
At 20 mA, the voltage drop is:
U ≈ 0.020 A · 7.12 Ω ≈ 0.142 V
In this example, the voltage drop caused by the cable alone is relatively small.
However, it may become relevant with significantly longer cables, smaller conductor cross-sections or additional series components.
Contact resistance at terminals, connectors and test leads must also be considered.
Particularly in older measuring circuits, corrosion, loose terminal connections or damaged cables can cause additional voltage drops.
These faults may also depend on temperature or mechanical movement.
The current loop should therefore not be evaluated solely on the basis of the calculated copper conductor resistance.
12. Distinguish Calibrator Output Capacity and Load Limits
The integrated loop power supply of a calibrator has its own electrical operating limits.
A specification such as “24 V loop power” initially describes a nominal function.
The permissible output current and guaranteed output conditions must also be considered.
Active mA sourcing may have its own load limits.
It is important to distinguish between a supply voltage for a passive 2-wire transmitter and the voltage range available to an active current source for regulating its output current.
The latter is frequently described as compliance voltage or the permissible load range.
A calibrator may, for example, provide 24 V loop power while supporting different maximum loads in active current sourcing mode.
Similarly, the internal loop supply is not necessarily suitable for powering an unlimited number of transmitters connected in parallel.
According to its technical documentation, the Druck DPI802, for example, provides 24 V ±10 % loop power with a maximum current of 35 mA.
This current value describes an instrument-specific limit of the corresponding supply function.
It does not mean that every connected device under test can be operated at 35 mA regardless of its load and minimum supply voltage.
The actual available supply voltage and permissible load conditions remain decisive.
For the Druck UPS4E, the integrated 24 V loop supply and the measuring and output functions covering 0 … 24 mA are documented.
However, a specific maximum external load must not be inferred from these specifications alone without further information.
The necessary details must be obtained from the relevant operating instructions or instrument specifications.
13. Correctly Connect 2-Wire, 3-Wire and 4-Wire Transmitters
Not every transmitter with a 4–20 mA output has the same electrical connection arrangement.
In a 2-wire transmitter, power is supplied through the same circuit that transmits the analogue measurement signal.
Such a transmitter can be operated using the designated 24 V loop power function of a suitable calibrator.
A 3-wire transmitter commonly has a supply connection, a shared reference connection and a separate signal output.
This arrangement requires different wiring and may require a separate power supply.
A 4-wire transmitter typically has separate supply terminals and a corresponding signal output.
This output may, for example, be active or passive.
Terminal designations and electrical requirements are instrument-specific.
Therefore, a 24 V loop supply must not be connected solely because the instrument has a 4–20 mA output.
During testing, it must be established whether the calibrator is intended to replace an external power supply or simply measure the existing output signal.
With an active 4–20 mA output, it must also be checked which load it can drive.
In this case, the corresponding burden calculation relates to the transmitter’s current output stage and not automatically to the calibrator’s internal loop power supply.
14. Choose the Correct Test Setup with Internal or External Power
For calibration, it must be determined whether the transmitter will be powered by the calibrator’s internal supply or the existing plant supply.
These two arrangements may create different electrical conditions.
On a laboratory bench, the measuring circuit may be very short and consist only of the calibrator and transmitter.
During plant operation, however, the PLC input, additional resistors and long cables may also form part of the circuit.
A transmitter may therefore easily deliver 20 mA in the laboratory but fail to reach the corresponding output value in the actual installation because the burden is too high.
Conversely, a weak internal calibrator supply may cause problems that do not occur when using a sufficiently rated plant supply.
The test must therefore match its intended objective.
If only the transmitter’s measuring characteristic is to be verified, a suitable stable supply with an adequate voltage margin is appropriate.
If the electrical function of the complete installed measuring circuit is to be investigated, its actual loads and supply conditions must be taken into account.
When a calibrator with internal 24 V loop power is used, an impermissible parallel connection to an existing active power supply must be avoided.
The procedure must comply with the operating instructions and the intended safe testing method.
Additional connection and equipment requirements apply particularly to Ex measuring circuits.
15. Systematically Measure Voltage Drops Under Actual Load
The calculated voltage budget provides an important basis. For reliable fault diagnosis, the actual voltages should also be measured.
Measurement directly at the transmitter’s supply terminals is particularly useful.
This allows the voltage actually available at a particular loop current to be verified.
For example, if the transmitter requires at least 12 V but only 11.5 V is present at its terminals at 20 mA, the required minimum operating voltage has already been exceeded in the wrong direction.
A measurement only at the calibrator output terminals may fail to reveal this condition.
The voltage drops across individual loads can also be investigated.
For an ohmic measuring resistor, the expected voltage can be calculated from current and resistance and compared with the measured value.
A significant deviation may indicate a different actual resistance, incorrect wiring or additional contact resistance.
In DC measuring circuits, voltage measurement is normally performed in parallel with the relevant component.
Current measurement, on the other hand, requires a suitable series connection.
These two connection methods must not be confused.
Particularly during troubleshooting, care must be taken to ensure that the measurement does not unintentionally alter or short-circuit the current loop.
Appropriate test equipment approved for the voltages and operating location must be used.
16. Test 4 mA, 12 mA, 20 mA and Overrange Conditions Separately
A complete loop test should not be performed exclusively at 4 mA or 12 mA.
The voltage drop across resistive loads increases proportionally with the current.
In many applications, the highest loop currents therefore place the greatest demands on the power supply.
Typical test points for a linear 4–20 mA transmitter include 4, 8, 12, 16 and 20 mA.
These represent 0, 25, 50, 75 and 100 % of the configured measuring range.
For evaluating the voltage margin, the highest actual intended output current is also relevant.
This may exceed 20 mA because of overrange output or fault current signalling.
Depending on configuration, currents of 21 or 22 mA may be relevant, for example.
The exact limit must not be assumed universally but must be obtained from the transmitter specification.
If the load is too high, deviations may occur particularly at the upper test points.
A current indication that rises correctly at low values but reaches an obvious limit at high values is especially suspicious.
Such behaviour may indicate an insufficient voltage margin.
However, it may also have other causes, such as incorrect output scaling or a defective output stage.
The voltage actually present at the transmitter should therefore also be recorded at the relevant test points.
17. Check Supply Stability, Battery Condition and Dynamic Behaviour
Portable process calibrators are frequently powered by batteries or rechargeable battery packs.
The available operating time depends on the functions used and the electrical load.
An activated 24 V loop supply can consume significantly more energy than passive current measurement alone.
Some manufacturers therefore specify different operating times for the various functions.
For the Druck DPI802, for example, longer operating times are documented in measuring-only mode than when using the internal 24 V supply.
However, a declining battery charge must not automatically be interpreted as an immediate voltage drop at the output.
Many instruments have internally regulated voltage supplies.
Whether and how the available output capacity changes at low battery levels depends on the instrument design.
For demanding tests, the operating conditions specified for the calibrator should therefore be maintained.
Time-dependent behaviour must also be considered.
If a transmitter briefly draws a different current during start-up or activates additional functions, temporary load conditions may arise.
Likewise, rapid current changes may temporarily place greater demands on the available voltage margin.
For a reproducible calibration procedure, the system must be allowed to stabilise sufficiently after switching on and after changing the test point.
The required time depends on the device under test, the calibrator and the particular measurement task.
18. Evaluate Reference Accuracy and Calibration Measurement Uncertainty
Electrical calibration requires suitable reference measuring instruments with sufficiently low measurement uncertainty.
The accuracy specification of a process calibrator is an important starting point.
However, it does not automatically describe the measurement uncertainty of the complete calibration.
Additional influences may arise from the device under test, its stability, electrical power supply, contact resistance and actual test conditions.
During transmitter calibration, it is first necessary to distinguish which measurement quantity is being evaluated.
If a pressure transmitter is being tested, for example, the reference pressure and output current must be considered together.
The calibrator’s current measurement uncertainty is then only one contribution to the overall uncertainty budget.
A supply voltage problem must not be confused with a normal measurement deviation within the calibration tolerance.
If the transmitter fails to reach its intended current value because of insufficient supply voltage, the test conditions may be outside its specification.
Such a measurement should not be treated as a valid calibration point without appropriate evaluation.
It is therefore useful to document the supply used and the existing burden.
The calibration status of the reference measuring instruments must also be traceable.
Whether factory calibration, ISO calibration or DAkkS-accredited calibration is required depends on the technical and quality assurance requirements of the measurement task.
When evaluating measurement uncertainty, the accuracy specifications used must be interpreted correctly.
For example, a specification expressed as a percentage of reading must be evaluated differently from one expressed as a percentage of full scale.
Additional digits, temperature coefficients and long-term stability may also be relevant.
19. Consider Reverse Polarity, External Power and Ex Requirements
When working with 4–20 mA current loops, the electrical operating and safety limits of the instruments must be observed.
Particularly during field testing, a measuring circuit may already be powered by an external supply.
If the calibrator’s internal 24 V supply is additionally connected without a suitable circuit arrangement, an impermissible connection between active voltage sources may result.
Polarity must also be observed.
Incorrect wiring may prevent the transmitter from starting or cause a protection function to operate.
Whether instrument damage can result depends on the available protective circuitry and permissible electrical limits.
The supply arrangement and terminal assignments must therefore be clearly established before connecting the calibrator.
Special requirements apply in potentially explosive atmospheres.
The normal 24 V loop supply of a calibrator must not automatically be used in an intrinsically safe circuit.
Even if a calibrator has an Ex-approved configuration, the permissible electrical parameters and intended connection method must be considered.
In intrinsically safe measuring circuits, the respective connection parameters and required verification of intrinsic safety are relevant, among other factors.
The Druck UPS4E, for example, is also available as the intrinsically safe UPS4E-IS version.
Corresponding Ex versions are also available for other process calibrators.
However, using an Ex-approved configuration does not replace verification of the actual measuring circuit conditions.
The protective functions of the existing process must also be considered.
Active current simulation may, for example, influence a PLC input connected to a control or alarm function.
Such tests must therefore only be performed according to the safe procedure specified for the installation.
20. Perform a Systematic Testing and Calibration Procedure
Testing a 24 V loop power supply should involve more than checking the output current.
A complete evaluation must consider the actual supply voltage, all relevant loads and the transmitter’s current range.
The following procedure describes a general technical testing sequence. Actual implementation depends on the manufacturer’s instructions and the safety requirements of the installation.
- Define the test task: Determine whether a transmitter is to be calibrated, a PLC input tested or the complete current loop investigated.
- Identify the device under test: Record the transmitter type, output signal, electrical connections and permissible supply range.
- Determine the circuit type: Distinguish between 2-wire, 3-wire and 4-wire instruments and between active and passive signal outputs.
- Check the supply arrangement: Determine whether the measuring circuit already has an external supply or requires the calibrator’s internal loop power.
- Select the calibrator: Check suitable operating modes, 24 V functionality, current measuring range, load limits and accuracy.
- Review the wiring diagram: Identify all loads actually connected in series and the intended connection terminals.
- Determine the burden: Consider PLC inputs, external measuring resistors, HART resistors and cable resistance.
- Account for internal burden: Evaluate the voltage drop caused by any additional series-connected current measurement instruments.
- Calculate the voltage margin: Determine the voltage remaining at the transmitter for the maximum required loop current.
- Check the HART configuration: Verify whether a suitable load resistor is already present and whether additional resistors are actually required.
- Establish the test setup: Connect the instruments according to the intended wiring diagram and under safe conditions.
- Switch on loop power: Establish the specified operating condition and verify that the transmitter starts.
- Check the voltage at the transmitter: Measure the actual operating voltage directly at the appropriate terminals of the device under test.
- Test the lower range point: Evaluate operation at 4 mA or the lower range value.
- Record additional test points: Verify suitable intermediate values and the upper range value.
- Evaluate maximum current: Where relevant and permitted for the application, include overrange or fault current conditions.
- Evaluate stability: Document supply voltage, output current and measurement behaviour under the specified load conditions.
- Identify the cause of deviations: Investigate supply voltage, burden, calibrator and transmitter function separately.
- Repeat the test: After any permitted corrective action, verify the relevant test points again under defined conditions.
- Document the results: Record supply conditions, loads, test points, references, measurement uncertainty and any deviations identified.
Testing at high currents is particularly important.
A successful test at 4 mA does not automatically prove that the supply is sufficient at 20 mA or at an intended overrange current.
Likewise, a correctly indicated current on the calibrator does not necessarily mean that sufficient operating voltage is available at every connected instrument.
The actual voltage conditions are therefore an essential part of measuring circuit diagnostics.
21. Diagnose Typical Fault Patterns and Their Causes
An insufficient voltage margin can produce symptoms similar to those of a defective transmitter or incorrect configuration.
The following overview shows typical observations and suitable diagnostic approaches.
| Observation | Possible Cause | Suitable Check |
|---|---|---|
| Transmitter does not start | No supply, incorrect connection method or reverse polarity | Check operating mode, terminal assignment and voltage directly at the transmitter |
| 4 mA is correct, but 20 mA cannot be reached | Insufficient voltage margin caused by high burden | Measure voltage drops at high loop current |
| Current remains at approximately 18–19 mA | Output limiting, excessive load or incorrect scaling | Check transmitter voltage, load and configuration separately |
| Measuring circuit no longer operates correctly after enabling the HART resistor | Additional 250 Ω resistor exceeds the available voltage budget | Investigate the effective load and whether the additional resistor is necessary |
| Current is correct in the laboratory but not in the plant | Additional PLC burden, cabling or other loads | Compare the complete plant circuit with the laboratory test setup |
| Current changes after connecting a second measuring instrument in series | Additional internal burden from the measuring instrument | Evaluate the voltage drop caused by the additional test instrument |
| Calibrator reports an overload or switches off loop power | Internal supply limit reached or wiring fault | Check output specifications, current consumption and electrical connections |
| Loop current is unstable | Marginal supply voltage, contact problems or unstable device under test | Record the supply voltage and current over time under load |
| HART communication does not work, but analogue current is correct | Unsuitable communication load, connection or configuration | Investigate HART impedance, connection and communication configuration |
| Calibrator does not simulate current in the existing installation | Active and passive operating modes confused | Check the external power supply and selected simulation function |
| Current value is correct, but PLC indication is wrong | Incorrect scaling or unsuitable input | Check the current input and PLC scaling separately |
| Calibration result changes after replacing the test leads | Contact or cable problem, possibly affecting the voltage margin | Inspect test leads and connections |
The listed causes are diagnostic indications and not definitive proof of individual faults.
Particularly with a transmitter that does not reach its upper current value, the voltage actually available should be checked first.
Changing the transmitter calibration may not eliminate the cause if the measuring circuit is operating outside its electrical limits.
The possible causes must therefore be investigated separately for a reliable assessment.
22. Suitable Loop and Process Calibrators from ICS Schneider
22.1 Druck UPS4E: Compact Loop Calibrator with 24 V Power Supply
The Druck UPS4E is a compact calibrator for testing and troubleshooting 4–20 mA current loops.
The instrument can measure and source electrical currents in the range from 0 … 24 mA.
The documented accuracy for the corresponding ranges is ±0.01 % of reading plus the specified counts.
An integrated 24 V loop power supply allows suitable 2-wire transmitters to be tested without a separate voltage source.
The UPS4E also incorporates a 250 Ω resistor to support HART applications.
The current measurement and sourcing functions are complemented by automatic step, ramp and other test programmes.
The voltage measurement function up to ±30 V DC is also useful for service work.
This allows existing supply voltages and certain voltage drops to be investigated.
The instrument also features a data logger with a capacity of up to 100,000 readings.
The UPS4E is therefore particularly suitable for testing individual process current loops, troubleshooting during maintenance and checking PLC inputs.
When calculating the maximum permissible burden, the specified limits of the supply or output operating mode being used must be considered.
The nominal 24 V function alone is not sufficient for this purpose.
The intrinsically safe UPS4E-IS version is also available for potentially explosive atmospheres.
22.2 Druck DPI620G Genii: Multifunction Calibrator with Loop Power
The Druck DPI620G Genii is a modular process calibrator for electrical, temperature and pressure calibration tasks.
Depending on the instrument configuration, it can measure or simulate current, voltage, resistance, thermocouple and RTD signals, as well as frequency quantities, among others.
Corresponding loop power functions are available for testing suitable 2-wire transmitters.
Depending on configuration and operating mode, the DPI620G platform supports an internal 24/28 V power supply.
The selected voltage, maximum available current and corresponding load capacity must be checked for the actual application.
HART and other digital communication functions are also available depending on the version.
This enables analogue output signals and digital device parameters to be investigated together as part of a testing task.
The DPI620G is particularly useful when different transmitter types must be tested and other electrical process signals must be generated or measured in addition to 4–20 mA.
Combined with suitable pressure modules and pressure stations, the platform can be expanded for comprehensive pressure calibration tasks.
22.3 Druck DPI610E: Pressure Calibration and Electrical Loop Testing in One Instrument
The Druck DPI610E combines pressure generation, a pressure reference and electrical calibration functions in a portable instrument.
Depending on the configuration, pneumatic measuring ranges up to 35 bar and hydraulic versions up to 1,000 bar are available.
The DPI610E supports measurement of the electrical output signals of process pressure transmitters and provides integrated power supply functions for suitable test arrangements.
The manufacturer documentation describes an internal 24 V supply for appropriate electrical measurement functions, among others.
The DPI610E also provides HART communication functions and options for documenting calibration results.
The combination is particularly useful for testing a 2-wire pressure transmitter because a defined test pressure can be generated while the output signal is checked simultaneously.
The available electrical voltage margin must also be considered here.
A correct reference pressure alone does not ensure that the connected transmitter can reach its intended output current when the electrical burden is too high.
The DPI610E is also available in corresponding intrinsically safe configurations for Ex applications.
22.4 Druck DPI802: Portable Instrument with 24 V Loop Power and HART Resistor
The Druck DPI802 combines pressure measurement with electrical testing functions.
The instrument supports simultaneous measurement of pressure and mA.
An integrated loop power supply is provided for testing 2-wire transmitters.
The manufacturer documentation specifies 24 V ±10 % with a maximum supply current of 35 mA.
An internal 250 Ω HART resistor can also be switched into the circuit.
This must be considered when evaluating the total burden of the measuring circuit if it acts as an additional load in the respective connection arrangement.
The DPI802 provides a current measurement function with a documented range up to 55 mA.
It is therefore particularly suitable for service and calibration tasks involving process pressure transmitters.
When evaluating the voltage budget, it is important to consider that the tolerance of the internal supply and the loop current affect the available voltage margin.
The DPI802 can therefore be used both for actual transmitter calibration and for targeted investigation of supply voltage problems.
22.5 WIKA CPH7000: Portable Process Calibrator for Pressure and Electrical Testing
The WIKA CPH7000 is a portable process calibrator for testing pressure gauges, pressure transmitters and other suitable process instruments.
Depending on the configuration, an integrated pressure reference and manual pressure generation are available.
The pressure generation range extends from approximately −0.85 … +25 bar.
The instrument provides electrical measurement and output functions covering 0 … 24 mA as well as a 24 V DC supply.
Suitable transmitters can therefore be electrically powered and their output signals checked as part of a calibration task.
The CPH7000 also provides functions for creating and performing calibration routines and storing measurement data.
The data can be transferred through the designated interfaces for subsequent evaluation and documentation.
Accuracy up to 0.025 % FS is available for demanding pressure calibration tasks.
A corresponding Ex configuration allows use under appropriately approved conditions.
With the CPH7000, the electrical load limits and actual supply conditions of the connected measuring circuit must also be considered.
Further suitable instruments are available from ICS Schneider in the Process Calibrators / Electrical Calibrators category and the main Calibration Technology section.
23. Conclusion: Available Voltage Margin Matters, Not Just the 24 V Indication
An integrated 24 V loop power supply is a useful function of modern process calibrators.
It allows suitable 2-wire transmitters to be tested without a separate voltage source and simplifies many service and calibration tasks.
However, reliable evaluation requires more than establishing that the calibrator has a 24 V function.
The decisive factor is the voltage remaining at the transmitter under the actual load.
PLC inputs, HART resistors, cables and current measurement instruments can consume a substantial portion of the available supply voltage.
Particularly at high loop currents, the necessary voltage margin may be lost.
A measuring circuit that works at 4 mA will not necessarily operate reliably at 20 mA or at an intended overrange current.
The maximum external burden must therefore be determined from the actual available supply voltage, the transmitter’s minimum operating voltage and the highest required current.
The calibrator’s internal burden and the instrument-specific limits of its internal loop power supply must also be considered.
For complete diagnosis, the voltages must be measured directly at the transmitter and, where appropriate, across the individual loads.
Only when the electrical operating conditions are satisfied can the actual measurement error of a transmitter be reliably evaluated.
Determine the circuit type → Check the calibrator supply → Identify the transmitter’s minimum voltage → Determine all loads → Establish the maximum loop current → Calculate the voltage margin → Account for HART resistance and internal burden → Measure voltage under load → Verify 4–20 mA test points → Check overrange operation → Evaluate measurement uncertainty → Document the results
The most important practical principle is therefore: A 24 V loop supply does not guarantee sufficient operating voltage at the device under test. What matters is the remaining voltage after all actual loads in the measuring circuit have been taken into account.
24. Frequently Asked Questions About 24 V Loop Power from Calibrators
24.1 What Does 24 V Loop Power Mean on a Calibrator?
A calibrator with 24 V loop power can supply electrical power to a suitable 2-wire current loop under the specified operating conditions. This allows corresponding transmitters to be tested without an external 24 V power supply.
24.2 Is 24 V Always Available at the Connected Transmitter?
No. The actual available voltage depends on the output voltage under load and the voltage drops within the measuring circuit. PLC inputs, measuring resistors, cables and any series-connected test instruments reduce the voltage remaining at the transmitter.
24.3 What Is the Burden of a 4–20 mA Current Loop?
The burden describes the electrical load that the current loop or current output stage must drive. For a resistive load, the corresponding voltage drop is calculated by multiplying the loop current by the resistance.
24.4 How Much Voltage Is Dropped Across a 250 Ω Resistor at 20 mA?
According to Ohm’s law, U = 0.020 A · 250 Ω = 5 V. At 4 mA, the voltage drop is only 1 V. The supply voltage required for external loads therefore increases with loop current.
24.5 How Do I Calculate the Maximum Permissible Load at 24 V?
For a simplified resistive model, the transmitter’s minimum operating voltage is subtracted from the available supply voltage. The remaining voltage is divided by the maximum required loop current. Additional voltage margins and non-resistive voltage drops must be considered separately where applicable.
24.6 Why Does My Transmitter Fail to Reach 20 mA During Calibration?
One possible cause is an excessive burden combined with insufficient supply voltage. Incorrect scaling, a defective current output stage or other instrument problems are also possible. The voltage directly at the transmitter should be checked at high output current.
24.7 Why Does the Current Loop Work at 4 mA but Not at 20 mA?
With resistive loads, the voltage drop increases proportionally with current. Consequently, significantly more supply voltage is required at 20 mA than at 4 mA. If the transmitter’s minimum operating voltage is not maintained, its current regulation function may fail.
24.8 Why Must I Also Consider Overrange Currents of 21 or 22 mA?
Certain transmitters can use output currents above 20 mA for overrange or fault conditions, depending on their configuration. If these states must be transmitted reliably, the voltage budget must also be sufficient at the highest current required.
24.9 What Is the Purpose of a 250 Ω HART Resistor?
It helps provide suitable electrical load or impedance conditions for HART communication. If it acts as an additional series resistor, it also causes a DC voltage drop and affects the available voltage margin.
24.10 Do I Always Need an Additional HART Resistor?
No. Some measuring circuits already contain a suitable load, for example in the PLC input. Whether an additional resistor is required depends on the actual electrical conditions and the requirements of the HART instruments.
24.11 What Does the Internal Burden of a Calibrator Mean?
A current measurement function connected in series may itself cause a voltage drop. This is referred to as the internal burden or burden voltage. It must be included in the complete voltage budget unless it is already accounted for in the instrument specification being used.
24.12 Can I Use the Internal 24 V Loop Supply Together with an External Power Supply?
Such a connection must not be made without a suitable, explicitly specified circuit arrangement. Impermissibly connecting active supplies together can cause malfunctions or damage. The correct operating mode and wiring must comply with the operating instructions.
24.13 Is Active mA Sourcing the Same as 24 V Loop Power?
No. In active mA sourcing mode, the calibrator regulates a current for a suitable load. Loop power, on the other hand, provides the electrical supply required by a connected, suitably designed transmitter. The functions may have different electrical load limits.
24.14 Can a Long Connecting Cable Affect the Current Loop?
Yes. Cable resistance causes an additional voltage drop. The complete length of the outgoing and return conductors, their cross-sectional area and material are decisive. This influence can become relevant with long cables, small conductor cross-sections or additional contact resistance.
24.15 How Can I Determine Whether the Loop Supply Is Too Weak?
An important test is to measure the actual operating voltage directly at the transmitter at different loop currents. The upper range value and highest intended current are particularly informative. The measured voltages are compared with the required minimum operating voltage and manufacturer specifications.
24.16 What Information Should Be Documented During Calibration?
In addition to the actual measured values, the calibrator used, device under test, connection method, supply conditions, relevant loads and calibration status of the references should be recorded. When investigating voltage-related problems, additional voltage measurements under load are particularly useful.
24.17 Which Calibrators from ICS Schneider Provide 24 V Loop Power?
The ICS product range includes the Druck UPS4E, DPI802, DPI620G Genii, DPI610E and WIKA CPH7000, among others, with corresponding loop power functions. The actual available voltages, current limits and electrical operating modes depend on the respective instrument configuration.
24.18 What Information Does ICS Schneider Need to Select the Correct Calibrator?
The required information includes the type of device under test, circuit configuration, output signal and required current range. The transmitter’s minimum operating voltage, existing burdens, PLC input resistances, cabling conditions and any HART communication requirements are also important. Selecting the calibrator additionally requires information about internal loop power, active current sourcing, passive simulation, voltage measurement, accuracy, calibration uncertainty, data storage, documentation and any required Ex approval. If pressure or temperature signals must also be tested, the corresponding measurement quantities and required reference ranges must be specified.