The Evolution of the DRUCK UPS Loop Calibrator
UPS4E is a rugged and ultra-compact loop calibrator designed for single-handed operation. It is an essential tool for testing and powering mA control loops and mA devices in process automation. Ideal for instrument maintenance – with a clearly readable display and easy-to-use functions like step, span, and valve testing that save time.
UPS4E uses advanced electrical calibration technology to provide a reliable and cost-effective calibrator for current loops.
General Technical Specifications | |
---|---|
Internal memory | 100,000 data points (data logging) |
Operating temperature | -10 to 50 °C |
Storage temperature | -20 to 70 °C |
Ingress protection | IP54: Protection against dust and splashing water |
Relative humidity | 0 to 90 % RH, non-condensing |
Shock/Vibration | MIL-PRF-28800F Class 2 |
EMC | EN 61326-2-03 |
Electrical safety | EN 61010-1:2010, EN 61010-2-030:2012 |
Enclosure material | High-impact ABS |
Loop resistance high | Primary reading flashes on error |
Out-of-range reading | “—” flashing on display |
Approvals | CE marked |
Display | 72 × 42.5 mm, custom segmented display |
Dimensions (L × W × H) | 145 mm × 73 mm × 25 mm |
Weight | 300 g including batteries |
Power supply | 4 × 1.5 V AA alkaline batteries |
Battery life | Up to 72 h (measure mode), up to 18 h at 12 mA loop current |
Auto power-off | After 10 minutes without key press (can be disabled) |
Battery status | 4-segment battery symbol |
Electrical terminals | 2 gold-plated 4 mm sockets |
HART resistor | Optional 250 Ohm loop resistor |
Connectivity | USB-C for data transfer and firmware updates |
The graphical display is high-contrast with backlight and shows both the primary measurement and the percentage of the full-scale value.
Internal 24 V loop supply available in both measurement and source mode – ideal for system shutdowns.
Displays both mA and percentage values based on either 4–20 mA or 0–20 mA ranges.
Quickly perform linearity tests and zero/span adjustments. The valve mode allows seat testing and actuator setup.
Mode | 0% | 25% | 50% | 75% | 100% |
---|---|---|---|---|---|
4–20 mA linear | 4 | 8 | 12 | 16 | 20 |
0–20 mA linear | 0 | 5 | 10 | 15 | 20 |
4–20 mA flow | 4 | 5 | 8 | 13 | 20 |
0–20 mA flow | 0 | 1.25 | 5 | 11.25 | 20 |
4–20 mA span check | 4 | 20 | |||
0–20 mA span check | 0 | 20 | |||
4–20 mA valve | 3.8, 4, 4.2 | 12 | 19, 20, 21 | ||
0–20 mA valve | 0, 0.2 | 10 | 19, 20, 21 |
Adjustable step/ramp rate (1–599 seconds) for one-handed testing of loops, valves, and actuator behavior.
Function | Range | Resolution | Accuracy (1 year) % of reading + counts |
---|---|---|---|
mA output with external loop power | 20 mA | 0.001 | ±0.01% of reading + 1 count |
24 mA | 0.001 | ±0.01% of reading + 2 counts | |
mA measurement with external loop power | ±20 mA | 0.001 | ±0.01% of reading + 1 count |
±24 mA | 0.001 | ±0.01% of reading + 2 counts | |
mA output with internal loop power | 20 mA | 0.001 | ±0.01% of reading + 1 count |
24 mA | 0.001 | ±0.01% of reading + 2 counts | |
mA measurement with internal loop power | 20 mA | 0.001 | ±0.01% of reading + 1 count |
24 mA | 0.001 | ±0.01% of reading + 2 counts | |
Voltage output | ±20 V | 0.001 | ±0.01% of reading + 2 counts |
Voltage measurement | ±30 V | 0.001 | ±0.01% of reading + 2 counts |
(1) Accuracy includes temperature effects from 10 °C to 30 °C (50 °F to 86 °F).
For use outside this range, add 0.003 %/°C (0.015 %/°F).
Precise setting of values to 0.001 mA. Ideal for alarm trip testing.
For loop diagnostics and maintenance of voltage-controlled devices.
Stores over 100,000 data points. Logging can be activated manually via the display, with adjustable intervals. Data can be exported to a PC for further analysis.