Portable measuring device for rapid performance testing of above-ground and underground fire hydrants. It determines and documents static pressure, flow pressure and flow rate directly at the draw-off point – ideal for fire brigades, network operators, water utilities, municipalities and service providers.
- Annual inspection of hydrants to ensure operability as a firefighting water source and compliance with fire-protection regulations
- Fast on-site measurement with clear key figures (static/flow pressure, flow rate)
- Documentation-ready for performance and condition records
- Rugged design for field use
- Compatible with pillar and underground hydrants; common connectors, e.g. Storz-B
- Optional: integration of a system separator/backflow preventer in accordance with DVGW practice
- Carrying handles and fold-out feet
Material | Aluminium alloy, glass-fibre reinforced plastic |
---|---|
Max. operating pressure | 16 bar / 230 PSI |
Operating temperature | 10 °C to 60 °C |
Ingress protection | IP 65 |
Flow ranges |
|
Measuring accuracy | approx. 1 – 1.5 % (within the measuring ranges) |
Flow display |
|
Pressure display | bar or psi (factory preset on order) |
Power supply | Lithium-ion battery 3.7 V / 1,800 mAh, with mains charger |
Accessories (order separately) |
|
Measured variables
- Static pressure: line pressure without draw-off
- Flow pressure: pressure during draw-off
- Flow rate (l/min): delivery rate of the hydrant at a defined pressure
- Minimum residual pressure: verification value for assessing network security
Standards & practical reference
- DVGW W 405 / W 392: Provision of firefighting water via the drinking-water network (planning / fundamentals) and test intervals
- DVGW W 405-B1: Draw-off by the fire brigade incl. requirements for drinking-water protection (system separator / backflow prevention)
- DIN EN 14384 / DIN EN 14339: Product standards for pillar and underground hydrants (requirements / tests)
- DIN 14462: Planning, operation and inspection of non-public firefighting water systems (e.g. in buildings) | annual testing and documentation requirement
Note: The device is intended for measurement and documentation; evaluation is based on the above standards and/or local utility requirements.
Category | Flow rate | Simultaneous operation | Min. flow pressure | Max. flow pressure | Max. static pressure |
---|---|---|---|---|---|
Wall hydrant S | 24 l/min | 2 | 2 bar | 8 bar | 12 bar |
Wall hydrant F | 100 l/min | 3 | 3 bar | 8 bar | 12 bar |
Wall hydrant F | 200 l/min | 3 | 4.5 bar | 8 bar | 12 bar |
Pillar hydrant DN80 | 800 l/min | According to fire-protection concept | 8 bar | 12 bar | |
Pillar hydrant DN100 | 1,600 l/min | According to fire-protection concept | 1.5 bar | 8 bar | 12 bar |
Underground hydrant DN80 | 800 l/min | 8 bar | 12 bar |