Showing all 16 results

  • IF96001 interface module for RS485 communication with Nemo 96HD/HD+
  • Makes measured data and configuration parameters available via RS485
  • RS485 communication compatible with JBUS / MODBUS
  • Programmable address from 1 to 255
  • Selectable baud rates from 4,800 to 38,400 bit/s
  • Parity bit selectable as none, even or odd
  • Maximum bus length 1200 m, up to 255 devices with RS485 repeater
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96003 interface module with 2 independent and insulated pulse outputs
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • Remote repetition of energy counting for active and/or reactive energy
  • Programmable pulse weight and pulse duration
  • Pulse duration selectable as 50, 100, 200 or 300 ms
  • 2 opto-relay outputs with potential-free SPST-NO contacts
  • Up to 2 modules per meter possible, providing a total of 4 pulse outputs
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96004 interface module with 2 independent and insulated analog outputs
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • Remote transmission of 2 electrical quantities via 0...20 mA or 4...20 mA
  • Programmable assignment of measured quantity as well as beginning and full-scale value
  • Unidirectional analog outputs with accuracy class 0.5
  • Output burden up to 750 Ω
  • Up to 2 modules per meter possible, providing a total of 4 analog outputs
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96005 interface module with 2 independent and insulated alarms
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • Monitoring of electrical quantities via programmable limit contacts
  • Programmable parameters: associated quantity, threshold, alarm type, relay state, hysteresis, intervention delay and reset delay
  • 2 relay outputs with potential-free SPST-NO contacts
  • Up to 2 modules per meter possible, providing a total of 4 alarms
  • Contact rating up to 5 A / 250 VAC or 5 A / 30 VDC
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96006 interface module for neutral current measurement
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • Direct connection up to max. 5 A or connection via external current transformer
  • Rated current 5 A / 1 A
  • True RMS measuring method with harmonic content up to the 22nd harmonic
  • Programmable current transformer ratio from 1 to 9999
  • Independent CT ratio for the neutral current transformer
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96007A interface module for PROFIBUS communication
  • Can be combined with Nemo 96HD, Nemo 96HD+ and Nemo 96HDLe
  • Makes measured data and configuration parameters available via PROFIBUS
  • PROFIBUS EN50170 – DP0 with transmission speed up to 12 Mb
  • Programmable address from 1 to 127
  • Galvanically insulated from measuring inputs and auxiliary supply
  • 9-pin connector
  • Plug-in module for connection to Nemo 96HD/HD+/HDLe
Datasheet
User Manual

  • IF96009 interface module for LONWORKS communication with Nemo 96HD/HD+
  • Enables integration of Nemo 96HD/HD+ meters into LONWORKS networks
  • FTT10 transceiver for LONWORKS communication
  • Transmission of key measured values such as voltage, current, power, frequency and energy
  • Galvanic insulation between input and auxiliary supply
  • Screw terminal for solid wires up to 4.5 mm² or flexible wires up to 2.5 mm²
  • Plug-in module for connection to the Nemo 96HD/HD+
  • Housing made of self-extinguishing polycarbonate
Datasheet
User Manual

  • IF96010 interface module for digital I/O and alarm inputs
  • Can be used with meters of the Nemo 96HD+ series
  • 2 potential-free contact inputs
  • 2 independent and resettable registers for pulse counting
  • 2 independent and insulated alarms
  • Allows monitoring of electrical quantities via alarms
  • Suitable for open / closed state indication and pulse counting via contact inputs
Datasheet
User Manual

  • IF96011 interface module for digital I/O and alarm inputs
  • Can be used with meters of the Nemo 96HD+ series
  • 2 digital inputs with 0...12 / 24 VDC voltage level
  • 2 independent and resettable registers for pulse counting
  • 2 independent and insulated alarms
  • Allows monitoring of electrical quantities via alarms
  • Suitable for state indication and pulse counting via digital voltage inputs
Datasheet
User Manual

  • IF96012 interface module with memory and RS485 communication for Nemo 96HD/HD+
  • Makes measured data and configuration parameters available via RS485
  • Internal memory for storing measured and energy data
  • Storage interval from 2 minutes, depending on data type and configuration
  • RS485 communication compatible with JBUS / MODBUS
  • Address, baud rate and parity programmable
  • Maximum bus length 1200 m, up to 255 devices with RS485 repeater
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96013 interface module for M-Bus communication with Nemo 96HD/HD+
  • Makes relevant measured data and configuration parameters available via M-Bus
  • M-Bus communication according to EN1434-3
  • Programmable address from 0 to 250
  • Selectable baud rates from 300 to 9,600 bit/s
  • Parity bit selectable as none, even or odd
  • Galvanic insulation between input and auxiliary supply
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet
User Manual

  • IF96014 interface module for RS485 communication with BACNET protocol
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • Makes relevant measured data available via BACNET communication
  • Suitable for integration into building automation and energy management systems
  • Communication via RS485 interface
Datasheet
User Manual

  • IF96015 interface module for Ethernet communication with Nemo 96HD/HD+
  • Makes relevant measured data available via Ethernet
  • Ethernet standard IEEE 802.3 with baud rate up to max. 10 Mb/s
  • Programmable network parameters such as IP address, subnet, gateway, TCP port and TCP timeout
  • Configuration via browser according to the module manual
  • RJ45 connection for Ethernet communication
  • Galvanic insulation between input and auxiliary supply
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet

  • IF96016 interface module for temperature measurement with Pt100 resistance thermometers
  • Can be combined with meters of the Nemo 96HD/HD+ series
  • 2 measuring inputs for Pt100 sensors
  • Measuring range -50...350 °C with 1 °C resolution
  • 2-wire connection via screw terminals
  • Pt100 linearization according to EN/IEC 60751
  • Burn-out detection in case of measuring circuit interruption
  • Plug-in module for connection to the Nemo 96HD/HD+
Datasheet

  • Interface module for harmonic analysis with Nemo 96HD+
  • IF96017 module for meters of the Nemo 96HD+ series
  • Analysis of voltage and current harmonics
  • Acquisition of voltage and current crest factors
  • Analysis of phase angles between voltages and currents
  • Suitable for extended power quality assessment
Datasheet

  • Radio communication interface for meters of the Nemo 96HD+ series
  • IF96018 module for wireless data communication
  • Transmits relevant measured data and configuration parameters via radio
  • Data communication from Nemo 96HD+ to Ethernet network
  • Radio transmission range up to 200 m in open space
  • Transmission frequency 868 MHz
Datasheet


Plug-in Interface Modules for NEMO 96 HD / HD+ / HDL

Plug-in interface modules for NEMO 96 devices expand communication and signaling capabilities without requiring additional DIN-rail space. These modules plug directly into the NEMO 96 meter and provide functions such as digital communication, pulse outputs or relay signaling. This enables efficient transmission of measurement values — energy, power, voltage, current or power-quality metrics — to higher-level systems or local monitoring equipment. The compact design makes upgrades easy and supports flexible adaptation to automation or energy-monitoring needs.

Questions & Answers on Plug-in Interface Modules

What are plug-in interface modules?

Modules that plug directly into NEMO 96 meters and add communication or signaling functions without external DIN-rail hardware.

Which functions can they provide?

Digital communication interfaces, pulse outputs, relay or alarm contacts, signal conversion and transmission of measurement data to automation or management systems.

Why use plug-ins instead of external modules?

They save space, simplify installation, integrate seamlessly with the meter and allow quick upgrades without modifying the cabinet layout.

Which data can be transmitted?

Energy, power, voltage, current, power factor and other electrical parameters supported by the NEMO 96 measurement device.

How are plug-in modules installed?

By inserting them into the designated plug-in slot of the NEMO 96 device; only interface wiring to the control or monitoring system is required.

Can multiple plug-ins be used at once?

This depends on the NEMO 96 model — many devices support one optional plug-in module.

What are the benefits?

Compact expansion, no extra DIN-rail space, easy retrofitting, flexible communication options and straightforward integration into monitoring or automation systems.

What are possible limitations?

Functionality depends on the plug-in variant; more complex communication tasks may still require external modules.

Where are plug-in interface modules typically used?

In energy monitoring, load supervision, industrial automation, building management systems or any application requiring digital access to measurement data.

Diese Website benutzt Cookies. Wenn du die Website weiter nutzt, gehen wir von deinem Einverständnis aus.