200A-3PH MK3 Secondary Current Injection


  • 0-50A three phase output
  • Clear and simple user interface
  • 3 phase current output
  • 0-50A per phase output current
  • True RMS digital metering
  • Memory ammeter
  • Multi-function timing system
  • Auxiliary metering input
  • Large back-lit liquid crystal display
  • Thermal and over-current protection
  • Compact and portable
  • 220V or 400V 3 phase mains supply options
  • 115V-440V 3 wire supply with optional supply transformer
Datasheet

The 200A-3PH Mk3 Secondary Current Injection test system provides commissioning and maintenance engineers with a compact, portable and flexible system for the testing and timing of protective relays, circuit breakers and thermal overloads. The unit is equally at home testing solid state or electro-mechanical relays, and has a rating suitable for testing thermal trips.

The 200A-3PH Mk3 has independent true RMS digital metering for each output, with independently selectable ranges.

The outputs are isolated and independently variable, and allow the injection of currents up to 200A. The outputs are protected by electronic over-current trips and fuses.

The timing system on the 200A-3PH Mk3 is flexible and exceptionally easy to use, allowing trip times to be measured to a high degree of accuracy. Units with auxiliary contacts may be timed using the NC or NO timer modes, and devices with no auxiliary contacts may be timed using the current operated mode. The unit is ideal for testing the following devices:

  • Over and under current relays
  • IDMT relays
  • Thermal overloads
  • Magnetic circuit breakers

The units may also be used in conjunction with the DVS3 Digital Voltage Source to test protection systems requiring three voltages and three currents. Protection that may be tested in conjunction with the DVS3 includes:

  • Directional relays
  • Distance protection
  • Power relays and transducers

Main Output

The units have three independently controlled outputs, one for each phase. The output is switched on and off by illuminated push buttons, and the current is set using the three control knobs on the front panel. All ranges are continuously variable from zero.

Range Continuous 5 minutes 1 minute
0-5V 50A 100A 200A

The above intermittent on-times must be followed by an off-time of 15 minutes, and are based on an ambient temperature of 25°C.

Auxiliary AC Outputs

A switched, isolated auxiliary 240V 50mA AC supply is available to power auxiliary control circuits. The output is protected by a fuse.

Digital Metering

The output on the 200A-3PH/ED is metered by a digital true RMS system with a 3.5 digit LED display. The range for each channel is independently selected for each channel by a switch on the front panel.

Range Resolution Trip current Accuracy
20.00A 0.01A 21.0A ±0.6% rdg+5d
50.00A 0.01A 52.5A ±0.6% rdg+5d
100.00A 0.1A 105.0A ±0.6% rdg+5d
200.00A 0.1A 210.0A ±0.6% rdg+5d

An electronic current trip is automatically set to 115% of full scale of the selected metering range to protect the device under test.

The unit is must be supplied by a 400V±10% 50/60Hz 3 phase 3300VA Max. The optional delta-star supply transformer allows the 400V unit to operate from other supply voltages.

A delta-star transformer is available as an optional accessory for operation from a 3 wire supply.
Temperature Range:

Storage -20°C to 60°C
Operating 0°C to 45°C

Timing System

The timing system on the 200A-3PH mk3 is very flexible, allowing a wide range of protective devices to be timed.

Range 0-999.999s
Resolution 1ms
Accuracy 0.01% rdg +1d (all except current operated mode)
0.01% rdg +3d (current operated mode)

The contact circuit has an open circuit voltage of 24Vdc and a short circuit current of 20mA. The contacts may be connected to volt-free contacts or contacts connected to a DC voltage system (240Vdc maximum).

The following functions are provided:

Mode Timer Start Timer Stop
Internal Start Press ‘ON’ Contact 1
Single Contact Contact 1 Contact 1
Dual contact Contact 1 Contact 2
Current operated Current > 20% of range Current < 20% of range

The output is automatically switched off at the end of the test to safeguard the relay under test.

Protection and Safety

The 200A-3PH mk3 Secondary Current Injection is protected by electronic over current trips on the outputs, fuses on the contact input, the mains input and regulators.

The auxiliary AC output is fuse protected on both units. An earth terminal is provided for connection to a local earth.

 

Weight 33 kg
Dimensions 315 × 550 × 300 mm
Supplied Accessories Operating manual
Mains lead
Spare fuse set
5m 200AL/3PH Output lead set
Optional Accessories 200A-3PH delta-star transformer, Part no. A178-0001








Technical advice: 03303 / 50 40 66

Technical advice for this product


    In accordance with the General Data Protection Regulation (GDPR), we are obliged to inform you about the collection of data. We meet this obligation by referring to our privacy notice.



    200A-3PH MK3 Secondary Current Injection

    • 0-50A three phase output
    • Clear and simple user interface
    • 3 phase current output
    • 0-50A per phase output current
    • True RMS digital metering
    • Memory ammeter
    • Multi-function timing system
    • Auxiliary metering input
    • Large back-lit liquid crystal display
    • Thermal and over-current protection
    • Compact and portable
    • 220V or 400V 3 phase mains supply options
    • 115V-440V 3 wire supply with optional supply transformer
    Datasheet

    The 200A-3PH Mk3 Secondary Current Injection test system provides commissioning and maintenance engineers with a compact, portable and flexible system for the testing and timing of protective relays, circuit breakers and thermal overloads. The unit is equally at home testing solid state or electro-mechanical relays, and has a rating suitable for testing thermal trips.

    The 200A-3PH Mk3 has independent true RMS digital metering for each output, with independently selectable ranges.

    The outputs are isolated and independently variable, and allow the injection of currents up to 200A. The outputs are protected by electronic over-current trips and fuses.

    The timing system on the 200A-3PH Mk3 is flexible and exceptionally easy to use, allowing trip times to be measured to a high degree of accuracy. Units with auxiliary contacts may be timed using the NC or NO timer modes, and devices with no auxiliary contacts may be timed using the current operated mode. The unit is ideal for testing the following devices:

    • Over and under current relays
    • IDMT relays
    • Thermal overloads
    • Magnetic circuit breakers

    The units may also be used in conjunction with the DVS3 Digital Voltage Source to test protection systems requiring three voltages and three currents. Protection that may be tested in conjunction with the DVS3 includes:

    • Directional relays
    • Distance protection
    • Power relays and transducers

    Main Output

    The units have three independently controlled outputs, one for each phase. The output is switched on and off by illuminated push buttons, and the current is set using the three control knobs on the front panel. All ranges are continuously variable from zero.

    Range Continuous 5 minutes 1 minute
    0-5V 50A 100A 200A

    The above intermittent on-times must be followed by an off-time of 15 minutes, and are based on an ambient temperature of 25°C.

    Auxiliary AC Outputs

    A switched, isolated auxiliary 240V 50mA AC supply is available to power auxiliary control circuits. The output is protected by a fuse.

    Digital Metering

    The output on the 200A-3PH/ED is metered by a digital true RMS system with a 3.5 digit LED display. The range for each channel is independently selected for each channel by a switch on the front panel.

    Range Resolution Trip current Accuracy
    20.00A 0.01A 21.0A ±0.6% rdg+5d
    50.00A 0.01A 52.5A ±0.6% rdg+5d
    100.00A 0.1A 105.0A ±0.6% rdg+5d
    200.00A 0.1A 210.0A ±0.6% rdg+5d

    An electronic current trip is automatically set to 115% of full scale of the selected metering range to protect the device under test.

    The unit is must be supplied by a 400V±10% 50/60Hz 3 phase 3300VA Max. The optional delta-star supply transformer allows the 400V unit to operate from other supply voltages.

    A delta-star transformer is available as an optional accessory for operation from a 3 wire supply.
    Temperature Range:

    Storage -20°C to 60°C
    Operating 0°C to 45°C

    Timing System

    The timing system on the 200A-3PH mk3 is very flexible, allowing a wide range of protective devices to be timed.

    Range 0-999.999s
    Resolution 1ms
    Accuracy 0.01% rdg +1d (all except current operated mode)
    0.01% rdg +3d (current operated mode)

    The contact circuit has an open circuit voltage of 24Vdc and a short circuit current of 20mA. The contacts may be connected to volt-free contacts or contacts connected to a DC voltage system (240Vdc maximum).

    The following functions are provided:

    Mode Timer Start Timer Stop
    Internal Start Press ‘ON’ Contact 1
    Single Contact Contact 1 Contact 1
    Dual contact Contact 1 Contact 2
    Current operated Current > 20% of range Current < 20% of range

    The output is automatically switched off at the end of the test to safeguard the relay under test.

    Protection and Safety

    The 200A-3PH mk3 Secondary Current Injection is protected by electronic over current trips on the outputs, fuses on the contact input, the mains input and regulators.

    The auxiliary AC output is fuse protected on both units. An earth terminal is provided for connection to a local earth.

     

    Weight 33 kg
    Dimensions 315 × 550 × 300 mm
    Supplied Accessories Operating manual
    Mains lead
    Spare fuse set
    5m 200AL/3PH Output lead set
    Optional Accessories 200A-3PH delta-star transformer, Part no. A178-0001








    Technical advice: 03303 / 50 40 66

    Technical advice for this product


      In accordance with the General Data Protection Regulation (GDPR), we are obliged to inform you about the collection of data. We meet this obligation by referring to our privacy notice.



      Diese Website benutzt Cookies. Wenn du die Website weiter nutzt, gehen wir von deinem Einverständnis aus.