The series consists of five transmitters:
- SITRANS LR100 – basic 4-20 mA measurement to 8 m with cable
- SITRANS LR110 – with communications, hazardous approvals options, and range to 15 m
- SITRANS LR120 – with communications, longest range to 30 m, and optional submergence shield for flooding protection
- SITRANS LR140 – basic measurements to 8 m with terminal connection
- SITRANS LR150 – with HART communication, hazardous approvals, local HMI option, and range to 15 m
Does your application have condensation? No problem.
Setup of the SITRANS LR100 is easy
Ignore obstacles in your application
- Easy Bluetooth® wireless technology for easy and quick setup with Siemens SITRANS mobile IQ App
- 80 GHz narrow beam and small size allows for the easiest installation and commissioning
- Custom radar microchip means signal killer conditions like condensation, buildup or fluffy solids are no match for the extreme sensitivity of the microchip, the weakest signals are still detected
- Zero blanking zone allows measurement range right up to the sensor and with an accuracy of 2 mm you can get rid of costly manual measurement methods
- Digitalization and Industry 4.0 ready with HART 7.0 or optional Modbus RTU for intelligent, value adding data locally or to the cloud
Detail
SITRANS LR100
|
SITRANS LR110
|
SITRANS LR120
|
SITRANS LR140
|
SITRANS LR150
|
|
---|---|---|---|---|---|
7ML530
|
7ML531
|
7ML532
|
7ML533
|
7ML534
|
|
Basic 4-20 mA measurement
to 8 m with cable |
With communications, hazardous approvals options, and range to 15 m
|
With communications,
longest range to 30 m, and optional submergence shield for flooding protection |
Basic measurement to 8 m
with terminal connection |
With HART communication,
hazardous approvals, l ocal HMI option, and range to 15 m |
|
Measuring pinciple
|
78-82 GHz, FMCW |
78-82 GHz, FMCW |
78-82 GHz, FMCW |
78-82 GHz, FMCW |
78-82 GHz, FMCW |
Measuring range
|
8 m (26 ft)
|
15 m (49 ft) |
30 m (98 ft)
|
8 m (26 ft)
|
15 m (49 ft)
|
Process connections
|
PVDF Thread 1½” and 1″
|
PVDF Thread 1½” and 1″
|
PVDF Thread 1″
|
PVDF Thread 1½”
|
PVDF Thread 1½”
|
Process pressure
|
-1 to 3 bar |
-1 to 3 bar |
-1 to 3 bar |
-1 to 3 bar |
-1 to 3 bar |
Process temperature
|
-40 to 60 °C (-40 to 140 °F)
|
-40 to 80˚C (-40 to 176˚F)
|
-40 to 80˚C (-40 to 176˚F)
|
-40 to 60 °C (-40 to 140 °F)
|
-40 to 70˚C (-40 to 158˚F) |
Accuracy
|
5 mm (0.2″)
|
2 mm (0.08″) |
2 mm (0.08″)
|
5 mm (0.2″)
|
2 mm (0.08″)
|
Beam Angle
|
8° |
8° |
4° |
8° |
8° |
mA/Loop,
Communications |
2-wire, 4 to 20 mA
|
2-wire, 4 to 20 mA/ HART or 4-wire, Modbus |
2-wire, 4 to 20 mA/ HART or 4-wire, Modbus |
2-wire, 4 to 20 mA
|
2-wire, 4 to 20 mA/HART
|
Ex approvals
|
no
|
Gas and dust
|
Gas and dust
|
no
|
Gas
|
Optional HMI
|
no
|
no
|
no
|
no
|
Yes, with Quick Start Wizard
and diagnostic support |
Bluetooth
|
yes
|
yes
|
yes
|
yes
|
yes
|