Technical specifications
| Primary rated current Ipr | 2000…5000 A |
|---|---|
| Rated frequency | 50 Hz |
| Operating frequency | 47…63 Hz |
| Option | Rated frequency 400 Hz, burden on request |
| Rated continuous thermal current Icth | According to EN/IEC 61869 |
| Thermal continuous current Ith | < 90 kA |
| Dynamic rated current Idyn | 2.5 Ith |
| Safety factor (FS) | ≤ 15 |
| Secondary rated current Isr | 1…5 A |
| Burden | 15…25 VA, see table |
| Accuracy class | Class 0.5 / 1, see table |
| Maximum power loss | ≤ 26 W at Icth |
| Note on thermal dimensioning | For thermal dimensioning of the control cabinet |
| Note on secondary winding | With open secondary winding, an operating time of 1 minute is guaranteed. |
| Operating note | Current transformers must not be operated with an open secondary winding in order to avoid potentially dangerous overvoltages and overheating. |