Frost protection thermostats are installed on the air side for the purpose of protecting air conditioning units, heat exchangers, radiators, and similar installations against damages due to frost or freezing. |
TWO-STAGE FROST PROTECTION THERMOSTAT (FTSE)
Control input signal | 0..10V= |
Temp. setpoint range | 1 … 10 oC |
Output Signal | 0..10V: Input/Temp. |
Ambient temperature | 15 … 15 oC |
Switch function/capacity | SPDT 250 Vac Microswitch / 8A |
Reset function | reset inside |
Thermostat application | frost protection thermostat, 2-phases |
Mounting place | air duct |
IP class | IP40 |
Power supply | 24 Vac | 7 VA |
Temperature element | capillary |
Setpoint device | inside |
Additional description | The 0-10V output signal is the maximum of the input signal and the temperature value (10-0 degrees C = 0-10V) |
Datasheet |