Using high frequency microwaves, the IFM2 level switch detects even non-conductive media. Foam and build-up remain undetected until the level reaches the measuring tip. By avoiding hidden edges and dead spaces, optimal cleaning and maintenance can be ensured. Various electrical connection options and a switching output allow easy integration. Dust and water ingress is reliably prevented by IP 67 protection. Feel free to contact us if you need a customization that is not listed in this datasheet.
Applications:
- Inteded for use in closed stainless steel containers
- Liquid media
- Industrial water applications
- Safety shutdowns
- Hygiene applications
Technical data:
Function | Contact output Max function„low in air“ / Min function„high in air“ |
Analog output | DC PNP, max 200 mA |
Power supply | 9…30 V DC |
Signal characteristics | Swich-on time approx. 1 s |
Teperature and pressure ranges | Medium temperature: 0..135 °C |
Surrounding temperature: -10…80 °C | |
Storage temperature: -40…85 °C | |
Operating pressure: max. 16 bar | |
Short-circuit resistance | Permanent |
Reverse polarity protection | Protection against reverse polarity, but no function |
Electromagnetic compatibility | Interference emissions and immunity acc. to EN 61326 |
Wetted materials | Housing: Stainless steel 1.4404 |
Sensor: PEEK | |
Protection type | IP 67 |
Weight | Approx. 150 g |