It supplies the transmitter with power and transmits the measuring signal with high accuracy galvanic isolated to the output. Alternative the measuring input accepts active 0/4 to 20 mA signals from 4-wire transmitters.
In addition to the analog signal, the DC 52500 also transmits data protocols for HART communication. It allows bidirectional communication with the field device from every point of the cabling.
The auxiliary power can be supplied via the connection terminals or via the optional In- Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.
Product line
Device Type | Order No. |
---|---|
Repeater Power Supply, bidirectional HART transmission | DC 52500 S |
Repeater Power Supply, bidirectional HART transmission, In-Rail-Bus for power supply |
DC 52500 B |
Technical Data
Input
Input signal | 0/4 to 20 mA | (4 to 20 mA with HART signal) |
Input resistance | ≤ 50 Ohm | |
Over load | 50 mA / 30 V | |
Transmitter supply (Tx) | 16 V (open circuit voltage/short circuit current < 22 V/35 mA) | |
Communication signal | Bidirectional HART transmission, internal AC impedance 250 Ohm |
Output
Output signal | 0/4 to 20 mA | (4 to 20 mA with HART signal) |
Load | 0 to 600 Ohm (at 20 mA) | (230 Ohm to 600 Ohm with HART signal) |
Linear transmission range | –1 to +110 % | |
Residual ripple | < 10 mVrms |
General Data
Transmission error | < 0.1 % full scale | |
Temperature coefficient 1) | < 100 ppm/K | |
Cut-off frequency -3 dB | 100 Hz, > 2.5 kHz HART signal | |
Response time T99 | 7 ms | |
Test voltage | 3 kV AC, 50 Hz, 1 min, Input against output against power supply |
|
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
|
Protection against electrical shock 2) | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 |
|
Ambient temperature | Operation Transport and storage |
–25 °C to +70 °C (-13 to +158 °F) –40 °C to +85 °C (-40 to +185 °F) |
Power supply | 24 V DC, voltage range 16.8 V to 31.2 V DC, approx. 1.3 W | |
EMC 3) | EN 61326-1 | |
Approvals | UL (USA/Canada): UL 61010, Class I, Div. 2 ATEX / IECEx: Zone 2 (nA) |
|
Construction | 6.2 mm (0.244″) housing, protection class: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Connection | Captive plus-minus clamp screws Wire cross-section max. 2.5 mm² / AWG 14 Stripped length 6 to 8 mm / 0.28 in Screw terminal torque 0.8 Nm / 7 lbf in |
|
Weight | Approx. 70 g |
- Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
- For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
- Minor deviations possible during interference
Block diagram

Dimensions

Terminal assignments
- 1 +Transmitter supply voltage U Tx
- 2 +Input current
- 3 −Input GND
- 4n.c.
- 5 +Output
- 6 −Output
- 7 +Power supply 24 V DC
(connected to In-Rail-Bus) - 8 −Power supply 24 V DC
(connected to In-Rail-Bus)
Optional power connection via In-Rail-Bus (see accessories)