Vortex FP and Vortex FP Compact are ATEX certified Exd Flameproof gas detector control panels for use in Zone 1 or Zone 2 hazardous areas such as on offshore production platforms or within refineries. Both offer all of the standard Vortex features, as well as a display fitted with magnetic switches which enable the system to be interrogated or inhibited without opening the system enclosure.
Simple to Use
- All the day-to-day operations can be completed via push buttons on the front panel – removing the requirement for hot-work permits to complete everyday tasks
- Fault and alarm LEDs on the front panel – providing instant indication of system status
- Alarm and channel settings can be adjusted at the panel
Highly flexibile
- Available in two sizes, including a compact format – for use in areas where space is a limiting factor
- Uses Vortex PC software – customisation is easy and user-friendly
- Uses industry standard Modbus RTU (or optionally Profibus) communications links – simple to integrate with PLC, DCS or SCADA control systems
Robust and Reliable
- Water and dust resistant to IP66
- All relays are monitored continuously – ensuring full functionality
Specifications
Vortex | Vortex Rack/Panel | |
Size | 440 x 640 x 332mm (17.3 x 25 x 13 ins) | 450 x 330 x 289mm (17.6 x 13 x 11.4 ins) |
Weight | 70Kgs (154lbs) approx. | 37.5kgs (83lbs) approx. |
Enclosure material | LM25 aluminium with polyester powder coating | |
Ingress protection | IP66 | |
Channels | Up to 12 (1 to 3 4-way input modules) | |
Operating temperature | -10°C to +40°C (14°F to +140°F) | |
Humidity | 0-95% RH non-condensing | |
Inputs | Gas 2 or 3 wire 4-20mA (sink or source), 0-5V | |
Fire – smoke & heat detectors, manual call-points Up to 3 loops, Up to 20 devices per loop | ||
Outputs | External audible/visual alarm drive Via relays, four 24Vdc 0.5A supplies provided. | |
Relays | Type Up to 32 SPCO with bus extension module | Relay limitations: 1 or 2 input modules: 2 relay modules max. (16 relays) 3 input modules: 1 relay module only (8 relays) |
Assignment – Common Battery back-up not available | ||
Assignment – Voting Alarms, faults and system events | ||
Relay modes Energised/de-energised, latched/non-latched, time-delayed, pulsed | ||
Digital communications | DCS/PLC/PC: RS-485 Modbus or Profibus Local configuration link: RS-232 (configuration software and lead supplied) |
|
Event logging | Up to 300 alarm, power, fault, system events are stored in Non-Volatile Memory | |
Panel indication | Channel number: 2-digit 7-segment Green LED Gas reading: 4-digit 7-segment Red LED Measurement units: % LEL, ppm, % Vol, Fire Power: Green LED Battery OK: Green LED Run/hold indication: Green LED Channel test mode: Flashing Amber LED System fault – integrity watchdog: Amber LED Displayed information can be altered and outputs can be inhibited during calibration using a magnetic key |
|
Alarm indication | Audible – internal sounder: Piezo Visual – Alarm: Level 1 & 2, Red LED; Fault – Per channel, Amber LED; Inhibit – Per zone, Amber LED |
|
Power | AC mains/DC: 110 or 240Vac 3.2A max 150W PSU 20 – 30Vdc | 85 – 264Vac 0.8A max 75W PSU 20 – 30Vdc |
Battery back-up: not available | ||
Approvals | Low voltage directive: EN61010-1 EMC: Directive 2014/30/EU: EN50270, FCC: CRF47 Part 15, ICES-003 ATEX: Ex II 2G D Zone 1, Zone 2, IECEx optional |
|
Functional safety | Validated to IEC61508 |