Designed for machine rooms, laboratories and unclassified areas, the Sensitron SMART3-R detector provides detection of explosive, toxic and refrigerant gases in safe (unclassified) areas.
With a 4-20 mA output, an RS485 communication bus and a 3-relay board, the circular LED indicator on the front displays the status of the instrument and an internal buzzer is activated in the event of a fault and/or alarm.
The instrument is controlled and calibrated via a keypad with STS/CKD+ display, with a protection rating of IP42. On request, the SMART3-R can be supplied in a version with an additional remote head and a 5m 6-pole cable included.
SMART3-R complies with the following regulations:
- EN 378-3
- EN 14624
- EN 50676
- IEC 60335-2-40 Annex LL
- ISO 5149-3
- F-Gas Regulation
Ideal for Machine Rooms & Light Industry
- Detects explosive, toxic and refrigerant gases in safe (unclassified) areas
- RS485 communication bus and a 3-relay board
- Multicolour LED ring and internal buzzer provide clear alarms, so you can act quickly to secure your site
- Controlled and calibrated via a keypad with STS/CKD+ display
- Simple sensor replacement
- Continuous self-diagnostics
-
Infrared sensor
Customisable
- Wide range of sensors and gas detection options to suit your needs
- Version with optional remote head
- Data logger exportable with STS/CKD-OLED or STS/CSW+
- On request 90-240 Vac but without 4-20 mA output
- The SMART3-R can be supplied in a version with an additional remote head and a 5m 6-pole cable included
Fully Compliant
- SMART3-R complies with the following regulations:
- EN 378-3
- EN 14624
- EN 50676
- IEC 60335-2-40
- Annex II
- ISO 5149-3
- F-Gas Regulation
- The detector has a protection rating of IP42
Specifications
With catalytic sensor | With infrared sensor | With electrochemical sensor | |
Size | Box: 120 x 120 x 52 mm Cover: 130 x 130 x 22 mm Remote head box: 106 x 106 x 56 mm |
||
Weight | Detector: 0.45kg Remote head: 0.3kg |
||
Enclosure material | Polycarbonate | ||
Ingress protection | IP42 | ||
Connection | 2 entries with M20 cable glands 6 optional entries for M16 cable glands |
||
Power | 12-24 Vdc or 90-240Vac | ||
Electrical output | 3 relays; RS485 serial output, 4-20 mA analogue output (only for 12-24 Vdc version) |
||
Operating temperature | -40 / +60°C -40 / +50°C 230V version |
-40 / +60°C (-10 / +50°C infred sensor for ppm refrigerant gases) -40 / +50°C 230V version (-10 / +50°C infred sensor for ppm refrigerant gases) |
-30 / +50°C |
Humidity | 0 / 95% RH non condensing | 15 / 90% RH non condensing | |
Compliance | EMC EN 61000-6-3:2007 + A1:201; EN 50270:2015 Electrical safety (90-240 Vac version) EN 61010-1: 2010 / A1: 2019 Refrigeration Standards EN 378-3; EN 14624; EN 50676; IEC 60335-2-40 Annex LL; ISO 5149-3; F-Gas Regulation |
Gases
Sensor type | |
Flammable Gases | MPS |
Hydrogen (H₂) | MPS |
Methane (CH₄) | Catalytic, Infrared, MPS |
LPG | Catalytic |
Propane (C₃H₈) | Catalytic, Infrared |
Butane (C₄H₁₀) | Catalytic, Infrared |
Petrol Vapour | Catalytic |
Oxygen (O₂) | Electrochemical |
Carbon monoxide (CO) | Electrochemical |
Ammonia (NH₃) | Electrochemical |
Chlorine (Cl₂) | Electrochemical |
Hydrogen sulphide (H₂S) | Electrochemical |
Sulphur dioxide (SO₂) | Electrochemical |
Nitrogen dioxide (NO₂) | Electrochemical |
Carbon dioxide (CO₂) | Electrochemical |
Sulphur hexafluoride (SF₆) | Infrared |
R152a | Infrared |
R454b | Infrared |
R32 | Infrared |
R1234yf | Infrared |
R1234ze | Infrared |
R134a | Infrared |
R404a | Infrared |
R407c | Infrared |
R410a | Infrared |
R1233zd | Infrared |
R125 | Infrared |
R407a | Infrared |
R407f | Infrared |
R449a | Infrared |
R507a | Infrared |
R417a | Infrared |
R448 | Infrared |
Refrigerants
Sensor Type | Refrigerant Type | |
SF6 | Infrared | F-gas (Switchgear) |
R290 | Infrared | Natural Refrigerant |
R600a | Infrared | Natural Refrigerant |
R744 | Infrared | Natural Refrigerant |