Designed to be installed in non-classified areas and car parks, the Sensitron SMART 3NC is a IP55 rated point gas detector for safe areas. Developed to provide an affordable solution for underground garages and non-hazardous locations, without compromising on sophisticated detection.
Available for Methane, LPG, petrol vapours, CO, NO2 and CO2, these detectors use an industrial catalytic sensor for flammable gases, a three-electrode electrochemical cell for CO and NO2 and an infrared sensor for CO2.
Offering seamless installation, the SMART 3NC’s maintenance and calibration can be done via the handheld keypad STS/CKD, while its ongoing system self-diagnosis ensure correct detector operation and performance at all times.
The SMART 3NC also has Relay and Modbus communication options.
Specifications
Catalytic sensor | Electrochemical cell | Infrared sensor | |
Size | Box: H100 x W100 x D52 mm (3.9 x 3.9 x 2ins) Cover: H105.8 x W105.8 x D7.8 mm (4.2 x 4.2 x 0.3ins) |
||
Weight | 0.25kg | ||
Enclosure material | Polycarbonate | ||
Ingress Protection | IP55 | ||
Connection | 2 x M20 | ||
Power | 12-24 Vdc | ||
Electrical output | Analogue 4-20 mA output; 1 or 3 relay board (optional); serial RS485 output (optional) | ||
Operating temperature | -20 / +60°C | -20 / +55°C | -20 / +60°C |
Humidity | 0 / 90% RH | 15 / 90% RH | 0 / 90% RH |
EMC compliance | EN 61000-6-3:2007 + A1:2011; EN 50270:2015 |
Gases
Sensor type | |
Methane (CH4) | Catalytic sensor |
Petrol Vapours | Catalytic sensor |
LPG | Catalytic sensor |
Carbon Monoxide (CO) | Electrochemical sensor |
Nitrogen Dioxide (NO2) | Electrochemical sensor |
Chlorine (CL2) | Electrochemical sensor |
Sulphur Dioxide (SO2) | Electrochemical sensor |
Hydrogen Chloride (HCL) | Electrochemical sensor |
Carbon Dioxide (CO2) | Infrared sensor |