Delat RD4B2 – Residual current device


  • Delta D4-S residual current device in 4-DIN-module housing
  • Selectable threshold from 30 mA to 30 A in 19 ranges
  • Instantaneous trip at IΔn 30 mA and adjustable intervention times up to 4.5 s
  • Instantaneous residual current display as percentage of IΔn via LED bar graph
  • Alarm function with pre-alarm or 2 SPDT contacts
  • Negative or positive relay safety selectable by DIP switch
  • Automatic permanent test and “no trip” test without output relay tripping
  • Manual or automatic reset with up to 10 restart attempts
Datasheet

Delta D4-S

Residual current device, 4 DIN modules

Type Residual current device for monitoring fault and leakage currents
Model Delta D4-S
Format 4 DIN modules according to DIN 43880
Input Low-voltage line with TD series transformer
Waveform Sinusoidal, AC type; chopped pulsating with superimposed DC component, A type according to EN 60947-2 Annex B and M / IEC 60947-2
Rated frequency 50 Hz
Working frequency 47…63 Hz
High-frequency note The effect of high-frequency current is less dangerous; therefore intervention with a higher IΔn value is allowed, making the device more immune to noise from line filters while remaining standards-compatible
Residual current setting Selectable by 7-position potentiometer, 3 ranges ×1 / ×10 / ×100
IΔn ranges 30 mA…30 A
Non-operating residual current 0.5 × IΔn
Intervention time Selectable by 7-position potentiometer
Intervention time ranges 0 / 0.06 / 0.15 / 0.31 / 0.5 / 1 / 4.5 s
Instantaneous trip t = 0 s at IΔn 30 mA
AL2 function Alarm with 2 SPDT contacts
AL50% function Alarm + 50 % IΔn pre-alarm
Alarm relay Negative or positive safety, selectable by DIP switch
Pre-alarm relay Negative safety, normally de-energized relay
Power-on signalling Green LED “ON”
Instantaneous value display LED bar graph with 4 yellow LEDs, 20 / 30 / 40 / 50 % of the set IΔn value; with IΔn higher than 70 %, 4 LEDs blink
Alarm intervention Red LED “TRIP” and relay switching
Ring current transformer-relay connection failure Red LED “TRIP” blinking and relay switching
Pre-alarm 50 % IΔn, relay switching
Manual test Verifies the residual current relay perfect working
Local test Front key TEST
Remote test By external contact, not available with RD4B21HB
Automatic continuous test Verifies the integrity of the connection between relay and ring core
“No trip” test Checks the working order of the earth leakage relay without switching the output relay
Local “no trip” test By TEST + RESET front keys, sequentially pressing RESET, then TEST and keeping it pressed
Alarm memorization Red LED “TRIP” and relay self-retaining
Reset Manual or automatic, selectable by DIP switch
Manual reset Local or remote
Automatic reset 10 attempts with different times
Reset time sequence 30 s / 1 min / 2 min / 4 min / 8 min / 16 min / 32 min / 64 min / 128 min / 256 min
Reset counter After 30 minutes from the first reset, the attempt counter automatically resets
Reset inhibit With persistent residual current > 50 % IΔn
Pre-alarm reset Automatically resets if the residual current is < 50 % IΔn
Output Alarm relay with 2 SPDT contacts or alarm + pre-alarm depending on function
Contact rating 5 A / 250 VAC at cosφ 1; 3 A / 250 VAC at cosφ 0.4; 5 A / 30 VDC
AC auxiliary supply 24 / 48 / 115 / 230 / 240 / 400 VAC
AC tolerance 0.85…1.1 Uaux; 40…60 V at Uaux 48 V
Auxiliary supply rated frequency 50 Hz
Auxiliary supply working frequency 47…63 Hz
AC power consumption ≤ 2.5 VA
DC auxiliary supply 20…150 VDC
Reverse polarity protection Available
DC power consumption ≤ 2.5 W
Short interruption of auxiliary supply Immunity up to 150 ms
Installation category III
Pollution degree 2
Insulation reference voltage 450 VAC / 130 VDC, depending on auxiliary supply
AC voltage test 2.5 kV R.M.S., 50 Hz / 1 min
Mounting 35 mm DIN rail
Rail type TH35-15 according to EN / IEC 60715
Connections Screw terminals for cable up to 4 mm²
Housing material Self-extinguishing polycarbonate
Protection degree IP40 front frame, IP20 terminals






Technical advice: 03303 / 50 40 66

Technical advice for this product


    In accordance with the General Data Protection Regulation (GDPR), we are obliged to inform you about the collection of data. We meet this obligation by referring to our privacy notice.



    Delat RD4B2 – Residual current device

    • Delta D4-S residual current device in 4-DIN-module housing
    • Selectable threshold from 30 mA to 30 A in 19 ranges
    • Instantaneous trip at IΔn 30 mA and adjustable intervention times up to 4.5 s
    • Instantaneous residual current display as percentage of IΔn via LED bar graph
    • Alarm function with pre-alarm or 2 SPDT contacts
    • Negative or positive relay safety selectable by DIP switch
    • Automatic permanent test and “no trip” test without output relay tripping
    • Manual or automatic reset with up to 10 restart attempts
    Datasheet

    Delta D4-S

    Residual current device, 4 DIN modules

    Type Residual current device for monitoring fault and leakage currents
    Model Delta D4-S
    Format 4 DIN modules according to DIN 43880
    Input Low-voltage line with TD series transformer
    Waveform Sinusoidal, AC type; chopped pulsating with superimposed DC component, A type according to EN 60947-2 Annex B and M / IEC 60947-2
    Rated frequency 50 Hz
    Working frequency 47…63 Hz
    High-frequency note The effect of high-frequency current is less dangerous; therefore intervention with a higher IΔn value is allowed, making the device more immune to noise from line filters while remaining standards-compatible
    Residual current setting Selectable by 7-position potentiometer, 3 ranges ×1 / ×10 / ×100
    IΔn ranges 30 mA…30 A
    Non-operating residual current 0.5 × IΔn
    Intervention time Selectable by 7-position potentiometer
    Intervention time ranges 0 / 0.06 / 0.15 / 0.31 / 0.5 / 1 / 4.5 s
    Instantaneous trip t = 0 s at IΔn 30 mA
    AL2 function Alarm with 2 SPDT contacts
    AL50% function Alarm + 50 % IΔn pre-alarm
    Alarm relay Negative or positive safety, selectable by DIP switch
    Pre-alarm relay Negative safety, normally de-energized relay
    Power-on signalling Green LED “ON”
    Instantaneous value display LED bar graph with 4 yellow LEDs, 20 / 30 / 40 / 50 % of the set IΔn value; with IΔn higher than 70 %, 4 LEDs blink
    Alarm intervention Red LED “TRIP” and relay switching
    Ring current transformer-relay connection failure Red LED “TRIP” blinking and relay switching
    Pre-alarm 50 % IΔn, relay switching
    Manual test Verifies the residual current relay perfect working
    Local test Front key TEST
    Remote test By external contact, not available with RD4B21HB
    Automatic continuous test Verifies the integrity of the connection between relay and ring core
    “No trip” test Checks the working order of the earth leakage relay without switching the output relay
    Local “no trip” test By TEST + RESET front keys, sequentially pressing RESET, then TEST and keeping it pressed
    Alarm memorization Red LED “TRIP” and relay self-retaining
    Reset Manual or automatic, selectable by DIP switch
    Manual reset Local or remote
    Automatic reset 10 attempts with different times
    Reset time sequence 30 s / 1 min / 2 min / 4 min / 8 min / 16 min / 32 min / 64 min / 128 min / 256 min
    Reset counter After 30 minutes from the first reset, the attempt counter automatically resets
    Reset inhibit With persistent residual current > 50 % IΔn
    Pre-alarm reset Automatically resets if the residual current is < 50 % IΔn
    Output Alarm relay with 2 SPDT contacts or alarm + pre-alarm depending on function
    Contact rating 5 A / 250 VAC at cosφ 1; 3 A / 250 VAC at cosφ 0.4; 5 A / 30 VDC
    AC auxiliary supply 24 / 48 / 115 / 230 / 240 / 400 VAC
    AC tolerance 0.85…1.1 Uaux; 40…60 V at Uaux 48 V
    Auxiliary supply rated frequency 50 Hz
    Auxiliary supply working frequency 47…63 Hz
    AC power consumption ≤ 2.5 VA
    DC auxiliary supply 20…150 VDC
    Reverse polarity protection Available
    DC power consumption ≤ 2.5 W
    Short interruption of auxiliary supply Immunity up to 150 ms
    Installation category III
    Pollution degree 2
    Insulation reference voltage 450 VAC / 130 VDC, depending on auxiliary supply
    AC voltage test 2.5 kV R.M.S., 50 Hz / 1 min
    Mounting 35 mm DIN rail
    Rail type TH35-15 according to EN / IEC 60715
    Connections Screw terminals for cable up to 4 mm²
    Housing material Self-extinguishing polycarbonate
    Protection degree IP40 front frame, IP20 terminals