| Primary rated current Ipn |
5…600 A |
| Rated frequency |
50 Hz |
| Operating frequency |
47…63 Hz |
| Option |
Rated frequency 400 Hz, burden to be defined |
| Rated continuous thermal current |
According to EN/IEC 60044-1 |
| Rated short-time thermal current Ith |
< 30 In |
| Dynamic rated current Idyn |
2.5 Ith |
| Safety factor (FS) |
≤ 5 |
| Secondary rated current Isn |
5…1 A |
| Burden |
20 VA at class 0.5 / 40 VA at class 1 |
| Accuracy |
Class 0.5 / 1 |
| Maximum power loss |
< 2.5 W |
| Max. temperature of passing cable / busbar |
125 °C |
| Note on secondary winding |
With open secondary winding during operation, an operating time of 1 minute is guaranteed. |
| Accessory |
ATAP015 (NT710) for automatic short-circuiting of the secondary winding when the limit value is exceeded |
| Auxiliary supply |
Not required, self-powered |