| Primary rated current Ipn |
50…80 A |
| Rated frequency |
50 Hz |
| Operating frequency |
47…63 Hz |
| Option |
Rated frequency 400 Hz, burden to be defined |
| Rated continuous thermal current Icth |
< 100 % Ipr |
| Thermal continuous current Ith |
< 30 In |
| Dynamic rated current Idyn |
2.5 Ith |
| Safety factor (FS) |
≤ 5 |
| Secondary current Isr |
5 / 1 A |
| Burden |
6 VA at class 0.5 / 7.5 VA at class 1 |
| Accuracy |
Class 1 / class 0.5 |
| Maximum power loss |
≤ 4.3 W |
| Note on thermal dimensioning |
For thermal dimensioning of the control cabinet |
| Note on secondary winding |
With open secondary winding, an operating time of 1 minute is guaranteed. |
| Accessory |
ATAP015 (NT710) for automatic short-circuiting of the secondary winding when the limit value is exceeded |
| Auxiliary supply |
Not required, self-powered |