| Primary rated current Ipr |
400…4000 A |
| Rated frequency |
50 Hz |
| Operating frequency |
47…63 Hz |
| Option |
Rated frequency 400 Hz, burden to be defined |
| Rated continuous thermal current Icth |
100 % Ipr |
| Rated short-time thermal current Ith |
< 60 Ipr, max. 90 kA |
| Dynamic rated current Idyn |
2.5 Ith |
| Safety factor (FS) |
≤ 5, protection class excluded |
| Secondary rated current Isr |
5 / 1 A |
| Burden |
3…20 VA for measurement / 3…50 VA for protection |
| Accuracy |
Class 0.5 / 1 for measurement, class 5P5 / 5P10 for protection |
| Maximum power loss |
≤ 44 W |
| Note on thermal dimensioning |
For thermal dimensioning of the control cabinet |
| Max. temperature of passing cable / busbar |
125 °C |
| Note on secondary winding |
With open secondary winding, an operating time of 1 minute is guaranteed. |
| Accessory |
ATAP015 (NT710) for automatic short-circuiting of the secondary winding when the limit value is exceeded |
| Auxiliary supply |
Not required, self-powered |