| Primary rated current Ipr |
750…4000 A |
| Rated frequency |
50 Hz |
| Operating frequency |
47…63 Hz |
| Option |
Rated frequency 400 Hz, burden to be defined |
| Rated continuous thermal current Icth |
100 % Ipr |
| Rated short-time thermal current Ith |
< 60 Ipr, max. 90 kA |
| Dynamic rated current Idyn |
2.5 Ith |
| Secondary rated current Isr |
5 / 1 A |
| Burden |
50…100 VA at class 5P / 15…35 VA at class 5P10 / 6…15 VA at class 5P15 / 1.5…4 VA at class 5P20 |
| Accuracy |
Class 5P / 5P10 / 5P15 / 5P20 |
| Maximum power loss |
≤ 34 W |
| Note on thermal dimensioning |
For thermal dimensioning of the control cabinet |
| Note on secondary winding |
With open secondary winding, an operating time of 1 minute is guaranteed. |
| Accessory |
ATAP015 (NT710) for automatic short-circuiting of the secondary winding when the limit value is exceeded |
| Auxiliary supply |
Not required, self-powered |