Overview
This flameproof (Exd) detector is housed within our high-grade aluminium alloy case. Certifications include gas and dust approvals for ATEX and IECEX with UL gas certification in progress.
Meet the next generation of flammable gas detection
The Xgard Bright is now available with MPS (Molecular Property Spectrometer™) technology
- Sensor Poisoning is solved
- Calibration is over
- TrueLEL™ multi-gas accuracy
- Hydrogen ready
Versatile:
- Flammable and toxic gas detection and oxygen monitoring – Reducing training requirements across sites
- Choice of M20 or ½”NPT connection – Supports multiple site requirements
- Low power requirement (~3W max) – Reducing site-wide power consumption
- IP65 or IP66 rating (with weatherproof cap) – Allows use in areas subject to regular wash downs or in exposed environments
Ease of installation and operation:
- Addressable – Drastically reduces the amount of cabling needed for multi-point installations
- Local display – Delivers gas level indication, status and supports maintenance routines
- Non-intrusive calibration – Removes the need to open the cover for calibration
- Plug in type terminal blocks: Making wiring quick and easy reducing installation costs
- Configuration via magnetic key – Reducing the amount of time operators spend in a hazardous area
Building on over 50 years of gas expertise, Crowcon is pioneering advanced molecular property spectrometer (MPS™) sensor technology that detects and accurately identifies 15 different flammable gases in one device
Specifications
Size | 156 x 166 x 109mm (6.1 x 6.5 x 4.3inch) |
Cable Entry | 2x M20 (stopping plug fitted to left-side entry) |
Power | 10-30Vdc. 3W max |
Electrical Output | 4-20mA current sink or source RS-485 Modbus RTU HART (Optional) |
Weight | Aluminium alloy 1kg (2.2lbs) |
Enclosure Material | ADC 12 aluminium alloy |
Relay | Alarm 1, Alarm 2, Fault
SPST contacts rated 1A 30Vdc |
Sounder Out | 24Vdc (nominally), 250mA maximum load |
Operating Temperature | -40°C to +70°C (-40°F to 158°F)
Note: sensor operating temperatures vary widely. Refer to the sensor module datasheet or contact Crowcon for specific sensor data. |
Humidity | 0 to 95% RH, non-condensing |
Repeatability | +/- 2% FSD |
Zero drift | +/- 2% FSD per year maximum |
Ingress protection | IP65 (IP66 with weatherproof cap) |
Approvals | ATEX and IECExEx II 2 G Ex db IIC T6 Gb
Ex tb IIIC T80ᶜ Db II 2 G Ex db IIC T6 Gb II 2 D Ex tb IIIC T80ᶜ Db Certificate numbers: TUV 16 ATEX 7908 X IECEx TUR16.0035 X |
EMC Compliance | EN50270: 2015 |
Standards | EN60079-0 :2012 + A11:2013 EN60079-1 :2014 IEC60079-0 :2011 Edition 6 IEC60079-1 :2014 Edition 7 |
Zones | Certified for use in Zone 1 and Zone 2 areas |
Gases and Ranges
Gas | Units | Max Range |
Standard Range |
Alarm 1 level |
Alarm 2 level |
Temp range °C |
MPS Flam | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Oxygen (O2) | %Vol | 30 | 25 | 19 (falling) | 17 (falling) | -20 to +50 |
Carbon Monoxide (CO) | PPM | 1000 | 250 | 30 | 200 | -30 to +50 |
Hydrogen Sulphide (H2S) | PPM | 100/200 | 25 | 5 | 10 | -30 to +50 |
Hydrogen (H2) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Methane (CH4) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Pentane (C5H12) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
LPG | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Carbon Dioxide (CO2) | %VOL | 0-5% | 0-5% | 0-2% | 0-3% | -20 to +50 |
PID (VOC) – Safe Area | PPM | 1000 | 1000 | 30 | 50 | -20 to +50 |
Infra Red Methane (CH4) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Infra Red Propane (C3H8) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Ammonia (NH3) – Safe Area | PPM | 100 | 50 | 25 | 25 | -20 to +40 |
Chlorine (CL2) – Safe Area | PPM | 10 | 5 | 1 | 3 | -20 to +40 |
Ozone (O3) – Safe Area | PPM | 1 | 1 | 0.1 | 0.2 | -20 to +40 |
Sulphur Dioxide (SO2) – Safe Area | PPM | 100 | 10 | 1 | 1 | -30 to +50 |
Infra Red Butane (C4H10) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Infra Red Pentane (C5H12) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |