Options
- Explosion protection for gases and dust
- Certificate of measuring equipment for Russian Federation
- Material certificate as per EN 10204-3.1
- Calibration certificate as per EN 10204-3.1
- Classification per SIL2
- EAC declaration (upon request)
Technical Data
Measuring ranges
See data sheet for detailed information |
Constructional design / case
Design: | Two-chamber case design with screw cap, continuously rotatable up to 170° Minimum case volume, excellent moisture and condensate protection |
Material: | Stainless steel mat.-no. 1.4301 (304) |
Degree of protection per EN 60529: |
IP 69K |
Climatic category per EN 60721 3-4: |
4K4H |
Window: | Non splintering plastic: Makrolon |
Case seal: | O-ring: NBR |
El. connection: | Screw terminal 1 mm2 |
Cable gland: | – Cable gland M16, material: PA – Circular connector M12 |
Further details see order code and upon request. | |
Weight: | approx. 1.2 kg (with 1 m capillary) |
Process connection
Design: | Volume reduced differential pressure chamber, suitable for the direct mounting of diaphragm seals with capillary connection. Diaphragm seals see product group D5. |
Material wetted parts
Material: | see product group D5 |
Measuring system
Sensor: | piezoresistive |
System filling: | Due to the application there are different system fillings available, see Technical Instruction TA_031. |
Accuracy
Limit point setting: | per DIN 16086 |
Reference conditions: | per EN 60770-1 |
Linearity errors: | ≤ 0.15 % of span TD 5:1 no modification |
Hysteresis: | ≤ 0.05 % of nominal range |
Repeatability: | ≤ 0.05 % of nominal range |
Calibration position: | Vertical mounting position (display facing upwards) |
Long-term drift: (EN 60770-1) | ≤ 0.1 % / year of nominal range |
Temperature influence of case: | Lower range value / upper range value Range 0…60 °C: ± 0.15 % / 10K of nominal range Range < 0 °C, > 60 °C: ± 0.2 % / 10K of nominal range |
Influence static pressure: | Refer to nominal range |
0.4 bar 0.12 % x stat. pressure [bar] x TD 1 bar 0.03 % x stat. pressure [bar] x TD 4 bar 0.02 % x stat. pressure [bar] x TD 16 bar 0.002 % x stat. pressure [bar] x TD 40 bar 0.001 % x stat. pressure [bar] x TD |
Output
General: | Delay time: approx. 160 ms |
Measuring cycle: 6 measurements / second | |
Measuring range setting: Turndown 5:1 | |
Basic module: 4…20 mA: | Signal: 4…20 mA, 2-wire |
Current range: 3.8…20.8 mA | |
Current limitation: approx. 22 mA | |
Alarm state: < 3.6 mA, optional > 21 mA | |
Damping: 0…120 seconds | |
Load RB: RB ≤ (UV-12V DC)/0,022A [Ohm] UV = supply voltage | |
Basic module: PROFIBUS PA: | Signal: digital per IEC 61158-2 |
Protocol: EN 50170-PROFIBUS PA, Profile 3.0 | |
Sensor address: 0…126 (126 = factory setting) | |
Power consumption: constantly 11 mA | |
Alarm current I FDE : 2 mA | |
Damping: 0…300 seconds | |
Parameterisation: SIMATIC PDM |
Supply voltage
Basic module: | 4…20 mA | PROFIBUS PA |
Standard design: | ||
Functional range: | 12…40 V DC | 9…32 V DC |
Ex-design: | ||
Functional range: | 12…30 V DC | 9…17.5 V DC |
Temperature ranges
Ambient: | -20…85 °C |
Media: | -40…400 °C * |
Storage: | -40…85 °C |
* depending on the design of the diaphragm seal and the system filling
Tests and certificates
See documents |
Type series
CV3330 |