The Signal Splitter/Repeater IS 21000 is used for isolation, conversion and distribution of 0/4 to 20 mA, 0/1 to 5 V and 0/2 to 10 V standard signals. The measuring input can also supply the loop power for 2-wire transmitters.
- Universal configurable operating
Signal isolator or repeater power supply for 2-wire transmitters, 2 independent outputs - Calibrated signal setting
Input and output range can be set by using DIP switch – high precision without any further adjustment - 4-Port isolation
Protection against erroneous measurements due to parasitic voltages or ground loops - Extremely slim design
6.2 mm slim housing for a simple and space saving DIN rail mounting - Optional In-Rail-Bus mounting rail connector
allows for fast and economical installation - Protective Separation acc. to EN61140
Protects service personnel and downstream devices against impermissibly high voltage - Maximum reliability
No maintenance costs - 5 Years Warranty
Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)
The Signal Splitter/Repeater IS 21000 is used for isolation, conversion and distribution of 0/4 to 20 mA, 0/1 to 5 V and 0/2 to 10 V standard signals. The measuring input can also supply the loop power for 2-wire transmitters.
The input and two isolated outputs can be easily configured by using DIP switch. Due to the calibrated range selection no further adjustment is necessary.
The auxiliary power can be supplied via the connection terminals or via the optional In- Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.
Input
Input signal (calibrated switchable) |
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V | |
Input resistance | Current input Voltage input |
≤ 35 Ohm ≥ 100 kOhm |
Overload | Current input Voltage input |
< 50 mA < 30 V |
Transmitter supply Tx (switchable) |
16 V (open circuit voltage/short circuit current ≤ 22 V/35 mA) |
Output I + II
Output signal (calibrated switchable) |
0 to 20 mA, 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V | |
Load | Current output: ≤ 6 V (300 Ohm at 20 mA) | Voltage output: ≤ 5 mA (2 kOhm at 10 V) |
Linear transmission range | -1 to +110 % | |
Residual ripple | < 10 mVrms |
General Data
Transmission error | < 0.1 % full scale | ||||||||||
Temperature coefficient 1) | < 100 ppm/K | ||||||||||
Cut-off frequency -3 dB | 5 kHz | ||||||||||
Response time T99 | 150 µs | ||||||||||
Test voltage | 3 kV AC, 50 Hz, 1 min, Input against Output I against Output II against power supply | ||||||||||
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 | ||||||||||
Protection against electrical shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. | ||||||||||
Ambient temperature | Operation Transport and storage |
–25 °C to +70 °C (-13 to +158 °F) –40 °C to +85 °C (-40 to +185 °F) |
|||||||||
Power supply | 24 V DC, voltage range 16.8 V to 31.2 V DC, approx. 1.4 W | ||||||||||
EMC 3) | EN 61326-1 | ||||||||||
Approvals |
|
||||||||||
Construction | 6.2 mm (0.244″) housing, protection class: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
||||||||||
Weight | Approx. 70 g |