The Isolation Amplifier IS 7400 is used for separation and conversion mV-signals such as those frequently used for current measuring with shunt-resistors or other applications.
- Calibrated signal setting
Input and output range can be set by using DIP switch – without any further adjustment - Universal power supply for 20 to 253 V AC/DC
Applicable world-wide for all common supply voltages - 3-port isolation
Protection against erroneous measurements due to parasitic voltages or ground loops - Ultra-small-sized housing
12.5 mm housing with plug-in screw terminal blocks - Maximum reliability
No maintenance costs - 5 Years Warranty
Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)
The Isolation Amplifier IS 7400 is used for separation and conversion mV-signals such as those frequently used for current measuring with shunt-resistors or other applications.
Its high level of reliability and cost optimized design make the IS 7400 the first choice in its class!
The desired input and output range can be easily set by using DIP switch and due to the calibrated range selection no further adjustment is necessary.
The slim housing with 12.5 mm width saves space in your switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly.
For range selection a simple housing unblocking is installed which makes it possible to reach easily all control elements also on the DIN-rail.
In cause of the new universal power pack for 20 to 253 V AC/DC the Isolation Amplifier IS 7400 is applicable world-wide for all common supply voltages. To control the power supply a green LED is installed on the front panel.
Input
Input signals | 0 to 60 mV, 0 to 150 mV, calibrated terminal selectable |
Input resistance | > 25 kOhm |
Input capacitance | Approx. 1 nF |
Overload | ≤ 30 V |
Output
Output signals | 0 to 10 V, 0 to 20 mA, 4 to 20 mA, calibrated switchable | |
Load | Current output Voltage output |
≤ 10 V (500 Ohm at 20 mA) ≤ 10 mA (1 kOhm at 10 V) |
Residual ripple | < 20 mVrms |
General data
Transmission error | < 0.3 % full scale | |
Temperature coefficient 1) | < 150 ppm/K | |
Cut-off frequency -3 dB | 1 kHz | |
Response time T99 | 0.7 ms | |
Test voltage | 2.5 kV AC, 50 Hz, 1 min., Input against output against power supply | |
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 | |
Ambient temperature | Operation Transport and storage |
–10 °C to +60 °C (+14 to +140 °F) –20 °C to +80 °C (-4 to +176 °F) |
Power supply | 20 to 253 V AC/DC | AC 48 to 62 Hz, approx. 3 VA DC approx. 1.5 W |
EMC 3) | EN 61326-1 | |
Construction | 12.5 mm (0.49″) housing, protection class: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Weight | Approx. 100 g |