Three-Phase Monitoring Relay
Relay for monitoring voltage asymmetry, phase failure and phase sequence
| Type | Three-phase monitoring relay for checking voltage asymmetry, phase sequence and phase loss |
|---|---|
| Network | Three-phase line 380…415 V, 50 and 60 Hz |
| Alarm functions | Wrong phase sequence or phase connection, lack of one or more phases, voltage asymmetry |
| Rated voltage | 380…415 V phase-phase |
| Waveform | Sinusoidal, form factor 1.11 |
| Rated frequency | 50…60 Hz, selectable |
| Rated burden | ≤ 2.7 VA |
| Voltage asymmetry threshold | Continuously adjustable by trimmer, range 5…25 % |
| Intervention time | Continuously adjustable by trimmer, range 0.2…10 s |
| Reset | Automatic |
| Power-on signalling | Green LED “ON” |
| Alarm signalling | Red LED “Alarm” and relay switching |
| Output | 1 SPDT relay contact |
| Contact rating | 5 A / 250 VAC at cosφ 1; 3 A / 250 VAC at cosφ 0.4; 5 A / 30 VDC |
| Execution | Positive safety, normally energized relay |
| Auxiliary supply | Supply taken from measurement, self-supplied |
| Installation category | III |
| Pollution degree | 2 |
| Insulation reference voltage | 450 V |
| Impulse withstand voltage | 5 kV, 1.2/50 µs, 0.5 J |
| Impulse test circuit | Input, relay output |
| AC voltage test 1 | 2.5 kV R.M.S., 50 Hz / 1 min |
| AC test circuit 1 | Input, relay output |
| AC voltage test 2 | 4 kV R.M.S., 50 Hz / 1 min |
| AC test circuit 2 | All circuits and earth |
| EMC | Emission tests according to EN 50081-1 / EN 55011, immunity tests according to EN 50082-2 |

Datasheet