For applications where one measuring range only is used, the Resistance Transmitters DR 41 offers a cost-effective alternative.
A cross-connector for the auxiliary power supply ensures fast and easy installation. The slim housing with 11.2 mm width saves significant space on the DIN-rail. If required a measuring range compensation can be performed at the Zero/Scan potentiometers behind the front cover.
Analog signal processing guarantees precise measured values with short response times and outstanding signal reproduction at the output.
Protective Separation and the 24 V AC/DC power supply make the DR 41 universally applicable for all measurement and industrial applications, as well as for building automation.
Product line
Devices | Sensor connection |
Order No. | ||
---|---|---|---|---|
2-wire connection 3-wire connection 4-wire connection |
DR 41 P – 2 DR 41 P – 3 DR 41 P – 4 |
X X X |
X X X |
|
Input | 0 … 20 Ohm | 2 | ||
0 … 50 Ohm | 3 | |||
0 … 100 Ohm | 4 | |||
0 … 200 Ohm | 5 | |||
0 … 500 Ohm | 6 | |||
0 … 1000 Ohm | 7 | |||
0 … 2000 Ohm | 8 | |||
0 … 5000 Ohm | 9 | |||
0 … 10 kOhm | A | |||
0 … 20 kOhm | B | |||
0 … 50 kOhm | C | |||
0 … 100 kOhm | D | |||
0 … 200 kOhm | E | |||
0 … 500 kOhm | F | |||
0 … 1 MOhm | G | |||
Output | 0 … 20 mA | 2 | ||
4 … 20 mA | 4 | |||
0 … 5 V | 5 | |||
1 … 5 V | 8 | |||
0 … 10 V | 6 | |||
2 … 10 V | 7 |
Technical Data
Input
Measuring range | Fixed ranges within 20 Ohm to 1 MOhm, see product line |
Sensor connection | 2-wire, 3-wire, 4-wire sensor connection, see product line |
Sensor wire resistance | < 25 Ohm / wire, maximum 5 % of final value at 2-wire connection |
Sensor current | 0.1 μA to 5 mA, depends on measuring range |
Output
Output signal | 0 to 20 mA, 0 to 5 V, 0 to 10 V, see product line 4 to 20 mA, 1 to 5 V, 2 to 10 V |
|
Load | Current output Voltage output |
≤ 500 Ohm ≥ 2 kOhm |
Residual ripple | < 10 mVrma |
General Data
Transmission error | < 0.2 % full scale | |
Temperature coefficient 1) | < 0.025 %/K | |
Zero/Span compensation | ± 5 % | |
Response time T99 | < 2 ms | |
Test voltage | 3 kV AC, 50 Hz, 1 min., input against output against power supply |
|
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
|
Protection against electrical shock 2) |
Protective separation according to EN 61140 by reinforced insulation in accordance with EN61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
|
Ambient temperature | Operation Transport and storage |
–20 °C to +60 °C (–4 °F to +140 °F) –35 °C to +85 °C (–31 °F to +185 °F) |
Power supply | 24 V AC/DC, ± 15 % | AC: 48 to 62 Hz, approx. 2 VA DC: approx. 0.7 W |
EMC 3) | EN 61326 -1 | |
Construction | 11.2 mm (0.44″) housing, protection class: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Connection | Wire cross-section max. 2.5 mm² | |
Weight | Approx. 50 g |
- Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
- For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
- Minor deviations possible during interference.
Block diagram

Dimensions
Terminal assignments
- 1Input R
- 2Input R
- 3Input 3-wire
- 4Input 4-wire
- 5 +Output
- 6 −Output
- 7Power supply 24 V AC/DC
- 8Power supply 24 V AC/DC