Temperature Transmitter DR 49 – Temperature Measuring with Pt1000-Sensors


The Temperature Transmitters DR 49 converts the sensor signal on input to temperature linear standard signal and makes it galvanic isolated available on output.

  • Cost optimized design
    Economical temperature measuring for standard applications with Pt1000 sensor with 2-wire or 3-wire connection
  • Only 60 mm installation depth, 11.2 mm wide
    Can be installed in economical standard terminal boxes
  • Fixed ranges, easy to use
    Ready to use without any settings or adjustments
  • Zero/Span compensation on front panel
    for readjustment of sensor signal or measuring equipment
  • True 3-port separation
    Protection against erroneous measurements due to parasitic voltages or ground loops
  • Protective Separation acc. to EN 61140
    Protects service personnel and downstream devices against impermissibly high voltage
  • Unlimited use with 24 V AC/DC power supply
    Universally applicable for all measurement and industrial applications
  • 5 Years Warranty
    Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)
Datasheet
User Manual

For applications where one measuring range only is used, the Temperature Transmitters DR 49 offers a cost-effective alternative.

A cross-connector for the auxiliary power supply ensures fast and easy installation. The slim housing with 11.2 mm width saves significant space on the DIN-rail. If required a measuring range compensation can be performed at the Zero/Scan potentiometers behind the front cover.

Analog signal processing guarantees precise measured values with short response times and outstanding signal reproduction at the output.

Protective Separation and the 24 V AC/DC power supply make the Temperature Transmitter DR 49 universally applicable for all measurement and industrial applications, as well as for building automation.

Product line

Devices Sensor Order No.
Pt 1000 DR 49 P – X X
Input 0…+50 °C 0
0…+100 °C 1
0…+150 °C D
0…+200 °C 2
0…+250 °C E
0…+300 °C 3
0…+350 °C F
0…+400 °C 4
-50…0 °C 8
-50…+50 °C 7
-50…+100 °C 6
-50…+150 °C 5
-50…+200 °C 9
-50…+250 °C A
-50…+300 °C B
-50…+350 °C C
-100…-50 °C Q
-100…0 °C R
-100…+50 °C S
-100…+100 °C T
-100…+150 °C U
-100…+200 °C V
-100…+250 °C W
-100…+300 °C Y
+50…+100°C G
+50…+150°C H
+50…+200°C J
+50…+250°C K
+50…+300°C L
+50…+350°C M
+50…+400°C N
+50…+450°C P
Output 0 … 20 mA 2
4 … 20 mA 4
0 … 5 V 5
1 … 5 V 8
0 … 10 V 6
2 … 10 V 7

Technical Data

Input

Sensor Pt 1000, 3-wire / 2-wire with bridge terminal 1 to 3
Measuring range Fixed ranges within -100 to +450 °C, see order information
Input error max. < 0.1 K + 0.05 % of span
Sensor wire resistance 25 Ohm / wire at 3-wire connection
Sensor current 0.1 mA

Output

Output signal 0 to 20 mA, 0 to 5 V, 0 to 10 V, see order information
4 to 20 mA, 1 to 5 V, 2 to 10 V
Load Current output
Voltage output
≤ 500 Ohm
≥ 2 kOhm
Residual ripple < 10 mVrms

General Data

Transmission error < 0.1 % full scale
Temperature coefficient 1) < 0.025 %/K
Zero/Span compensation ± 3 %
Response time T99 < 2 ms
Test voltage 3 kV AC, 50 Hz, 1 min., input against output against
power supply
Working voltage 2)
(Basic Insulation)
600 V AC/DC for overvoltage category II and pollution
degree 2 acc. to EN 61010-1
Protection against
electrical shock 2)
Protective separation according to EN 61140 by reinforced
insulation in accordance with EN61010-1 up to 300 V AC/DC
for overvoltage category II and pollution degree 2 between
all circuits.
Ambient temperature Operation
Transport and storage
–20 °C to +60 °C   (–4 °F to +140 °F)
–35 °C to +85 °C   (–31 °F to +185 °F)
Power supply 24 V AC/DC, ± 15 % AC: 48 to 62 Hz, approx. 2 VA
DC: approx. 0.7 W
EMC 3) EN 61326 -1
Construction 11.2 mm (0.44″) housing, protection class: IP 20
mounting on 35 mm DIN rail acc. to EN 60715
Connection Wire cross-section max. 2.5 mm²
Weight Approx. 50 g
  1. Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
  2. For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
  3. Minor deviations possible during interference.

Block diagram

Dimensions

Terminal assignments

  • 1Input Pt
  • 2Input Pt
  • 3Input 3-wire
  • 4
  • 5 +Output
  • 6 −Output
  • 7Power supply 24 V AC/DC
  • 8Power supply 24 V AC/DC








Technical advice: 03303 / 50 40 66

Technical advice for this product


    In accordance with the General Data Protection Regulation (GDPR), we are obliged to inform you about the collection of data. We meet this obligation by referring to our privacy notice.



    Temperature Transmitter DR 49 – Temperature Measuring with Pt1000-Sensors

    The Temperature Transmitters DR 49 converts the sensor signal on input to temperature linear standard signal and makes it galvanic isolated available on output.

    • Cost optimized design
      Economical temperature measuring for standard applications with Pt1000 sensor with 2-wire or 3-wire connection
    • Only 60 mm installation depth, 11.2 mm wide
      Can be installed in economical standard terminal boxes
    • Fixed ranges, easy to use
      Ready to use without any settings or adjustments
    • Zero/Span compensation on front panel
      for readjustment of sensor signal or measuring equipment
    • True 3-port separation
      Protection against erroneous measurements due to parasitic voltages or ground loops
    • Protective Separation acc. to EN 61140
      Protects service personnel and downstream devices against impermissibly high voltage
    • Unlimited use with 24 V AC/DC power supply
      Universally applicable for all measurement and industrial applications
    • 5 Years Warranty
      Defects occurring within 5 years from delivery date shall be remedied free of charge at our plant (carriage and insurance paid by sender)
    Datasheet
    User Manual

    For applications where one measuring range only is used, the Temperature Transmitters DR 49 offers a cost-effective alternative.

    A cross-connector for the auxiliary power supply ensures fast and easy installation. The slim housing with 11.2 mm width saves significant space on the DIN-rail. If required a measuring range compensation can be performed at the Zero/Scan potentiometers behind the front cover.

    Analog signal processing guarantees precise measured values with short response times and outstanding signal reproduction at the output.

    Protective Separation and the 24 V AC/DC power supply make the Temperature Transmitter DR 49 universally applicable for all measurement and industrial applications, as well as for building automation.

    Product line

    Devices Sensor Order No.
    Pt 1000 DR 49 P – X X
    Input 0…+50 °C 0
    0…+100 °C 1
    0…+150 °C D
    0…+200 °C 2
    0…+250 °C E
    0…+300 °C 3
    0…+350 °C F
    0…+400 °C 4
    -50…0 °C 8
    -50…+50 °C 7
    -50…+100 °C 6
    -50…+150 °C 5
    -50…+200 °C 9
    -50…+250 °C A
    -50…+300 °C B
    -50…+350 °C C
    -100…-50 °C Q
    -100…0 °C R
    -100…+50 °C S
    -100…+100 °C T
    -100…+150 °C U
    -100…+200 °C V
    -100…+250 °C W
    -100…+300 °C Y
    +50…+100°C G
    +50…+150°C H
    +50…+200°C J
    +50…+250°C K
    +50…+300°C L
    +50…+350°C M
    +50…+400°C N
    +50…+450°C P
    Output 0 … 20 mA 2
    4 … 20 mA 4
    0 … 5 V 5
    1 … 5 V 8
    0 … 10 V 6
    2 … 10 V 7

    Technical Data

    Input

    Sensor Pt 1000, 3-wire / 2-wire with bridge terminal 1 to 3
    Measuring range Fixed ranges within -100 to +450 °C, see order information
    Input error max. < 0.1 K + 0.05 % of span
    Sensor wire resistance 25 Ohm / wire at 3-wire connection
    Sensor current 0.1 mA

    Output

    Output signal 0 to 20 mA, 0 to 5 V, 0 to 10 V, see order information
    4 to 20 mA, 1 to 5 V, 2 to 10 V
    Load Current output
    Voltage output
    ≤ 500 Ohm
    ≥ 2 kOhm
    Residual ripple < 10 mVrms

    General Data

    Transmission error < 0.1 % full scale
    Temperature coefficient 1) < 0.025 %/K
    Zero/Span compensation ± 3 %
    Response time T99 < 2 ms
    Test voltage 3 kV AC, 50 Hz, 1 min., input against output against
    power supply
    Working voltage 2)
    (Basic Insulation)
    600 V AC/DC for overvoltage category II and pollution
    degree 2 acc. to EN 61010-1
    Protection against
    electrical shock 2)
    Protective separation according to EN 61140 by reinforced
    insulation in accordance with EN61010-1 up to 300 V AC/DC
    for overvoltage category II and pollution degree 2 between
    all circuits.
    Ambient temperature Operation
    Transport and storage
    –20 °C to +60 °C   (–4 °F to +140 °F)
    –35 °C to +85 °C   (–31 °F to +185 °F)
    Power supply 24 V AC/DC, ± 15 % AC: 48 to 62 Hz, approx. 2 VA
    DC: approx. 0.7 W
    EMC 3) EN 61326 -1
    Construction 11.2 mm (0.44″) housing, protection class: IP 20
    mounting on 35 mm DIN rail acc. to EN 60715
    Connection Wire cross-section max. 2.5 mm²
    Weight Approx. 50 g
    1. Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
    2. For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
    3. Minor deviations possible during interference.

    Block diagram

    Dimensions

    Terminal assignments

    • 1Input Pt
    • 2Input Pt
    • 3Input 3-wire
    • 4
    • 5 +Output
    • 6 −Output
    • 7Power supply 24 V AC/DC
    • 8Power supply 24 V AC/DC








    Technical advice: 03303 / 50 40 66

    Technical advice for this product


      In accordance with the General Data Protection Regulation (GDPR), we are obliged to inform you about the collection of data. We meet this obligation by referring to our privacy notice.



      Diese Website benutzt Cookies. Wenn du die Website weiter nutzt, gehen wir von deinem Einverständnis aus.