Dynisco SPX 5-Series Smart Pressure Sensors
The Dynisco SPX 5-Series is a smart 4–20 mA pressure transmitter range for general-purpose pressure measurement in hazardous locations. The sensors use an advanced algorithm to linearize offset effects caused by process conditions, providing precise and repeatable pressure measurements in demanding industrial applications.
These amplified transmitters eliminate the need for external signal conditioning and can be connected directly to DCS, PLC, computer and other high-level control systems. All models can be interface-configured, with optional remote configuration via HART™. Optional thermocouple or RTD configurations are available for melt temperature measurement.
| Technical Specifications | |
|---|---|
| Output Signal | 4–20 mA, with optional HART™ |
| Input Voltage | 16–36 VDC standard; 16–30 VDC ATEX intrinsically safe |
| Accuracy | All models ±0.20% |
| Repeatability | ±0.1% |
| Rangeability | 3:1 turndown |
| Overpressure | 2 × FSO or 35,000 psi, whichever is less; models 5390, 5391 and 5392: 1.5 × FSO for 10,000 psi |
| Zero Balance Adjustment Range | -40% to +10%; -80% to +20% for FSP < 500 psi |
| Load Resistance | 500 Ω at 24 VDC; 1,000 Ω at 36 VDC |
| Electronics Ambient Temperature | 70 °F (20 °C) |
| Electronics Operating Temperature | -29 °C to 85 °C |
| Maximum Diaphragm Temperature | 400 °C; models 5344, 5390, 5391 and 5392 limited to 315 °C |
| Electronics Compensated Temperature Range | -18 °C to 65 °C |
| Electronics Zero Shift | 0.01% FS/°F max. (0.02% FS/°C max.) |
| Electronics Span Shift | 0.01% FS/°F max. (0.02% FS/°C max.) |
| Snout Zero Shift | 5344/5390/5391/5392: 1 psi/100 °F typical from 75–450 °F; 2 psi/100 °F typical from 450–600 °F 5342/5343: 15 psi/100 °F typical |
| Mounting Torque | 5342: 500 inch-lbf max.; 5343: 50 inch-lbf max.; 5344: 350 inch-lbf max.; 5390: 350 inch-lbf max.; 5391: 350 inch-lbf max.; 5392: 80 ft-lbf max. |
| Standard Wetted Parts | DyMax-coated 15-5 PH stainless steel |
| Approvals | ATEX/IECEx intrinsically safe, FM & CSA explosion-proof, additional approvals available |
| Safety Certification | SIL2 for pressure output and PL “c” for relay output |