The switched-mode DC-DC converters type 2218.2 to 2218.8 are compact voltage converters for wall mounting. They are suitable for industrial applications, mobile electrical systems and technical installations where a defined output voltage must be supplied from an existing DC input voltage.
The series covers a rated output power range from 60 to 240 W. Depending on the version, nominal input voltages of 24 VDC, 48 VDC or 60 VDC are available. The input voltage ranges are 18 to 28 VDC, 42 to 56 VDC or 50 to 70 VDC depending on the type.
On the output side, versions with 5 VDC, 12 VDC or 24 VDC are available. Depending on the version, the units provide output currents of 5 A, 10 A or 20 A. The output voltage is stabilized and the CV ripple RMS value is 50 mV.
The converters are short-circuit protected and do not provide galvanic isolation between input and output. The settling time for load changes from 10 to 100 % is 1.5 ms. Depending on the type, cooling is provided by convection or by a fan.
Most versions provide IP30 protection rating and protection class III. Type 2218.8 is equipped with an aluminium die-cast enclosure and provides IP65 protection. Electrical connection is made via 6.3 mm flat connectors, M6 bolts or cables, depending on the type.
| Product | Switched-mode DC-DC converter |
| Device type | Voltage converter / switching regulator |
| Mounting | Wall mounting |
| Rated output power | 60 to 240 W |
| Versions | Type 2218.2 / 2218.3 / 2218.4 / 2218.5 / 2218.52 / 2218.6 / 2218.61 / 2218.7 / 2218.8 |
| Nominal input voltage type 2218.2 / 2218.3 | 24 VDC |
| Nominal input voltage type 2218.4 / 2218.5 / 2218.52 / 2218.8 | 48 VDC |
| Nominal input voltage type 2218.6 | 60 VDC |
| Nominal input voltage type 2218.61 / 2218.7 | 24 VDC |
| Input voltage range | 18 to 28 VDC / 42 to 56 VDC / 50 to 70 VDC depending on version |
| Output voltage type 2218.2 / 2218.4 / 2218.52 / 2218.61 | 12 VDC |
| Output voltage type 2218.3 / 2218.5 | 5 VDC |
| Output voltage type 2218.6 / 2218.7 / 2218.8 | 24 VDC |
| Output current | 5 A, 10 A or 20 A depending on version |
| Stability of Ua with change in Ue | 40 mV or 50 mV depending on type |
| CV stability, load 0-100 % | 250 mV |
| CV ripple RMS | 50 mV |
| No-load current consumption | 30 mA, 40 mA or < 60 mA depending on version |
| Current consumption at full load | 1.8 A to 11 A depending on version |
| Fuse | 4 A, 6.3 A or 2 x T6.3 A depending on version |
| Settling time, load 10-100 % | 1.5 ms |
| Cooling | Convection or fan depending on type |
| Operating temperature | 0 to 35 °C |
| Max. relative humidity | 85 % at 35 °C |
| Dimensions | 150 x 85 x 65 mm / 150 x 112 x 87 mm / 145 x 98 x 230 mm / 121 x 55 x 171 mm depending on type |
| Weight | 0.7 kg, 0.75 kg or 1.0 kg depending on version |
| Special features | E1 approval for type 2218.2, electronic overload protection, parallel connection possible, type 2218.8 with aluminium die-cast enclosure |
| Protection rating / class | IP30 / III, type 2218.8 with IP65 |
| Electrical input connections | 6.3 mm flat connectors, M6 bolts or cables depending on type |
| Electrical output connections | 6.3 mm flat connectors, M6 bolts or cables depending on type |
| Radio interference suppression | DIN VDE 0875 T 3 G |

Datasheet