Due to the easy configuration, the new universal power pack and the ultra-small housing the Isolation Amplifier is suitable for flexible use.
The ratiometric measuring method allows the acquisition of potentiometer signals without range selection. Unipolar and bipolar output signals can be selected with a DIP switch. Subsequent readjustment or measured range compensation can then be performed at the zero/scan potentiometers on the front panel.
The small housing with 12.5 mm width saves space in your switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. For range setting a simple housing unblocking is installed which makes it possible to reach easily all control elements on the mounting rail.
The new universal power pack for 20 … 253 V AC/DC means the DR 4310 can be used anywhere in the world, with all mains power supplies. The unit’s high efficiency contributes significantly to reducing the unit’s own heat generation. This is reflected in extremely high reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.
Product line
Devices | Order No. |
---|---|
Potentiometer Transmitter, configurable | DR 4310 AG |
Technical Data
Input
Input Signal | Potentiometer 100 Ohm to 100 kOhm |
Sensor supply | 1.2 V (limited to max. 5 mA) |
Potentiometer connection | 3 wire connection |
Input resistance | > 10 MOhm |
Output
Voltage | Current | |
Output signals (switch selectable) |
± 10 V, 0 to 10 V, 2 to 10 V ± 5 V, 0 to 5 V, 1 to 5 V |
± 20 mA, 0 to 20 mA, 4 to 20 mA ± 10 mA, 0 to 10 mA, 2 to 10 mA |
Load | ≤ 10 mA (1 kOhm at 10 V) | ≤ 12 V (600 Ohm at 20 mA) |
Linear transmission range | unipolar: –2 to +110 %, bipolar: –110 to +110 % | |
Residual ripple | < 10 mV rms |
General Data
Transmission error | < 0.1 % full scale | |
Temperature coefficient 1) | < 100 ppm/K | |
Zero/Span compensation | Start value 0 to 20 %; End value: 80 to 100 % Minimum span: 80 % |
|
Cut-off frequency -3 dB | 1 kHz, switchable to 30 Hz | |
Response time T99 | 0.8 ms, 20 ms | |
Test voltage | 4 kV AC, 50 Hz, 1 min., Input against output against power supply |
|
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
|
Protection against electrical shock 2) |
Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 600 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
|
Ambient temperature | Operation Transport and storage |
–20 to +70 °C (-4 to 158 °F) –35 to +85 °C (-31 to 185 °F) |
Power supply | 20 to 253 V AC/DC, | AC 48 to 62 Hz, approx. 2 VA DC approx. 1.0 W |
EMC 3) | EN 61326-1 | |
Construction | 12.5 mm (0.49″) housing, protection type: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Weight | Approx. 100 g |
- Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
- For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
- Minor deviations possible during interference
Block diagram

Dimensions
Terminal assignments
- 1Input, Wiper +
- 2 −Input, Poti +
- 3 +Input, Poti –
- 4–
- 5 +Output
- 6 −Output
- 7Power supply AC/DC
- 8Power supply AC/DC
Pluggable screw clamp terminals
Wire cross-section max. 2.5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)