Due to the calibrated selection of the input and output ranges, the new universal power supply and the ultrasmall housing the Isolation Amplifier is suitable for flexible use. The high reliability and the protective separation are further features, which ensure a safe system operation.
The desired input and output range can be easily set by using DIP switch and due to the calibrated range selection no further adjustment is necessary. Also the cutoff frequency can be adapted to the measurement task by using the DIP Switch. Alternatively, all signal combinations are also available in the form of fixed range units.
The slim housing with 12.5 mm width saves space in the switch cabinet and facilitates by the practical plug-in screw terminal blocks the assembly. A simple housing latch has been provided for range setting purposes to make all the operating elements, including those on the DIN-rail, easily accessible.
The new universal power pack for 20 … 253 V AC/DC means the DN 2000 can be used anywhere in the world, with all mains power supplies. The unit’s high efficiency contributes significantly to reducing the unit’s own heat generation. This is reflected in extremely high reliability and long-term stability. A green LED on the front of the unit has been provided to monitor the power supply.
Product line
Devices | Order No. | ||
---|---|---|---|
Isolation Amplifier, calibrated range selection | DN 2000 AG |
Technical Data
Input
Input signal | 0…20 mA, 4…20 mA, 0…10 V, calibrated switchable | |
Input resistance | Current input Voltage input |
22 Ohm 1 MOhm |
Input capacitance | Approx. 1 nF | |
Overload | Current input Voltage input |
≤ 200 mA Voltage limitation via 30 V Z-Diode, max. continuous current 30 mA |
Output
Output signal | 0…20 mA, 4…20 mA, 0…10 V, calibrated switchable | |
Load | Current output Voltage output |
≤ 12 V (600 Ohm at 20 mA) ≤ 10 mA (1 kOhm at 10 V) |
Linear transmission range | –2 … +110 % | |
Residual ripple | < 10 mVrms |
General Data
Transmission error | < 0.1 % full scale | |
Temperature coefficient 1) | < 50 ppm/K | |
Cut-off frequency -3 dB | 1 kHz, DN 2000 switchable to < 30 Hz | |
Response time T99 | 0.7 ms 20 ms | |
Test voltage | 4 kV, 50 Hz, 1 min., input against output against power supply | |
Working voltage 2) (Basic Insulation) |
600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
|
Protection against electrical shock 2) |
Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
|
Ambient temperature | Operation Transport and storage |
–20 °C to +70 °C –35 °C to +85 °C |
Power supply | 20 … 253 V AC/DC, | AC 48 … 62 Hz, approx. 2 VA DC approx. 1.0 W |
EMC 3) | EN 61326 -1 | |
Construction | 12.5 mm (0.49″) housing, protection classt: IP 20 mounting on 35 mm DIN rail acc. to EN 60715 |
|
Weight | Approx. 100 g |
- Average TC related to full scale value in specified operating temperature range, reference temperature 23 °C
- For applications with high working voltages, ensure there is sufficient spacing or isolation from neighboring devices and protection against electric shocks.
- Minor deviations possible during interference
Block diagram

Dimensions
Terminal assignments
- 1 +Input current
- 2 −Input current
- 3 +Input voltage
- 4 −Input voltage
- 5 +Output
- 6 −Output
- 7Power supply AC/DC
- 8Power supply AC/DC
Pluggable screw clamp terminals
Wire cross-section max. 2,5 mm², Multi-wire connection max. 1 mm² (two wires with same cross-section)